Troubleshooting and Common Questions

NI-FBUS Configurator User Manual

B-12

ni.com

Fisher Rosemount 3244MS rev3 (Link Master device) does not show
up on the bus.

The Fisher Rosemount 3244MS rev3 temperature transmitters are
intrinsically safe link master devices. With the default timing settings, they
do not appear on the bus. These devices require the tweaking of some bus
parameters for them to show up in the NI-FBUS Configurator. Revision 2
of the 3244MV works fine without these adjustments. These changes are
made by right-clicking the link (the top level in the hierarchy) and selecting
Advanced View. Now the MIB parameters appear underneath the
representation of the interface board. Double-clicking the MIB will bring
up a block configuration window where these values can be changed.

Make the interface

PRIMARY_LINK_MASTER_FLAG

parameter

FALSE

.

Make the interface

CONFIGURED_LINK_SETTINGS

match those of the

Rosemount device. The values for the

CONFIGURED_LINK_SETTINGS

on the Rosemount transmitter are

(in order): 10, 6, 5, 37, 0, 12, 186, 2, 1, 0, 4.

At the time of publication, Fisher Rosemount was advising customers to
make the following changes to the advanced settings.

Caution

Do not modify these parameters without good reason. If you must modify

parameters for certain devices, the device manufacturer will recommend settings.
Modifying these parameters can have an adverse affect on data throughput rates. If settings
are incorrectly modified, some devices may disappear off the bus.

Table B-1. Rosemount Advanced Parameter Settings

Parameter

Value

T1

0x17700

T2

0x1D4C00

T3

0x249F0

Slot Time

8 or higher

Maximum Response Delay

3 or higher

Minimum inter-PDU Delay

12 or higher

CONFIGURED_LINK_SETTINGS

Make the same for all link masters
on the link

Advertising