Chapter 3

NI-FBUS Configurator Tutorials

© National Instruments Corporation

3-3

NI-FBUS Configurator User Manual

7.

In the block configuration window, select the Scaling tab.

8.

Confirm the scaling parameters in particular and check that the other
parameters are reasonable.

9.

To change a parameter, place your mouse over the existing value and
click. Then, enter values appropriate for your device, as shown in the
following example.

XD_SCALE

EU_100

50

EU_0

–50

Units_Index

mV

Decimal

3

OUT_SCALE

EU_100

400

EU_0

–100

Units_Index

°C

Decimal

3

L_TYPEindirect

Note

Selecting an

L_TYPE

of

direct

results in no further scaling of the transducer value

(that is,

OUT_SCALE

is ignored). Normally, some type of output scaling is desirable, in

which case one of the indirect

L_TYPES

should be chosen. Refer to the

L_TYPE (Scaling)

parameter description of Chapter 4,

Parameters

, for more information.

10. When you are ready to write all the new values, click the Write

Changes button at the bottom of the window.

If you have already downloaded the configuration, you might get a
warning telling you that the block is in the wrong mode for the request.
This is because some devices allow certain parameters to be written
only in

OOS

mode. Acknowledge the warning and click the OOS

button. Allow a few seconds for the device to get into

OOS

mode before

clicking Write Changes again. After the changes have been written,
change the block back to its original mode. Another common cause for
warnings when writing changes is trying to write an invalid value to a
parameter. Devices will refuse values that are out of range. To correct
this problem, note the parameter that caused the warning and change it
to an appropriate value.

Advertising