RCAS_OUT (Process)

The back calculation output used by the supervisory host when establishing
a Remote cascade loop.

RCAS_OUT_D (Process)

The discrete back calculation output used by the supervisory host when
establishing a Remote cascade loop.

READBACK (Scaling, Tuning)

The valve or actuator position read back from the transducer, in transducer
units.

READBACK_D (Scaling, Tuning)

The transducer state for the actual discrete valve or actuator position.

RESET (Tuning)

The time constant for the integral component of the PID block. It is
measured in seconds per repeat (so larger values have less effect, and

INF

effectively disables the integral term).

RESTART (Diagnostic, Option)

Allows the user to restart the device remotely.

Caution

Using

Restart

to

Defaults

causes all your configured parameters in the

FP-3000 to revert to their factory default settings.

Table 4-19. Restart Values

Value

Behavior

Restart

Resource

Restarts the device.

Restart

to

Defaults

Restarts the device, restoring all parameter values to default values.

Restart

Processor

Restarts the device as if the power was cycled.