Function Block Modes

The most common operational modes for function blocks on devices are
Automatic (

Auto

), Cascade (

Cas

), Manual (

Man

), and Out Of Service

(

OOS

).

In Automatic mode, the block is running under its normal automatic
control, using a local setpoint value in the normal block algorithm to
determine the output value.

In Cascade mode, the block is receiving its setpoint value from another
function block for use in the normal block algorithm to determine the
output value. A linkage object makes the connection between the two
blocks. The linkage object is created implicitly when you wire the
output of one function block to the input of another as described in the

Create and Edit Function Block Applications

section. For example,

a PID function block receives its setpoints from an upstream block.

In Out Of Service mode, the block is not running at all. Normally, this
mode is used during block configuration. Some devices require that the
function block be in Out Of Service mode when changing certain
parameters.

In Manual mode, the block output is not being calculated by the normal
block algorithm. The operator writes the output of the block directly.

The MODE_BLK Parameter

The

MODE_BLK

parameter for a function block is the parameter that

contains information on the modes of the block. It has four fields:

TARGET

,

ACTUAL

,

PERMITTED

, and

NORMAL

.

PERMITTED

and

NORMAL

are defined

by the device manufacturer.

PERMITTED

contains a list of all allowable modes for that block.

NORMAL

is the mode the device manufacturer expects the block to be

in during normal operation.

ACTUAL

is the current operating mode of the function block on the

device.

TARGET

is a field that is writable by the user. Writing this field tells the

device to change to the specified mode. The device will attempt to
change the mode. If it is successful, the

ACTUAL

mode changes to

reflect the

TARGET

mode.