Mode Shedding Parameters

Mode shedding parameters handle communication failures with a host.

For remote modes in which the cascade input is periodically written by a
host application, Foundation Fieldbus provides mode shedding to handle
failure of the host application. For the

RCas

mode and

ROut

modes, there

are two timeout parameters in the resource block:

SHED_RCAS

and

SHED_ROUT

. If the block is in a remote mode and the block input being used

(

RCAS_IN

or

ROUT_IN

) is not updated within the timeout period, the block

sheds to a higher priority mode. The action taken by the block when mode
shedding occurs is defined by the

SHED_OPT

parameter, as described in the

table below. The shed condition ends when the host writes the remote input
parameter. If a normal return shed option is selected, the block attempts to
enter the original remote mode. If a no return shed option is selected, the
target mode is changed at the time the block sheds mode, and the block does
not attempt to enter the original lower priority mode when the shed
condition ends.

Option Parameters

Table 4-6. Mode Shedding Parameters

RCAS_IN

SHED_OPT

RCAS_IN_D

SHED_RCAS

ROUT_IN

SHED_ROUT

Table 4-7. Option Parameters

CLR_FSTATE

SET_FSTATE

CONTROL_OPTS

SHED_OPT

FAULT_STATE

SIMULATE

FEATURE_SEL/FEATURES

SIMULATE_D

FSTATE_TIME

SP_HI_LIM

FSTATE_VAL

SP_LO_LIM

FSTATE_VAL_D

SP_RATE_DN

GRANT_DENY

SP_RATE_UP

Advertising