ROUT_IN (Mode Shedding, Process)

The cascade input set by a remote host. This is propagated to the output of
the block when it is in

ROut

mode. If the block is in

ROut

mode and this

parameter is not updated in

SHED_ROUT

time (a parameter in the resource

block), the block enters mode shedding. Mode shedding allows the block
to degrade from

ROut

mode into some higher priority mode.

ROUT_OUT (Process)

This is the back calculation output used by the host when trying to establish
a remote output loop. While the loop is being established, it is the current
value of the output channel and can be used by the host to initialize for
smooth transfer of control.

RS_STATE (Diagnostic, Process)

The current state of the device.

SEL_1 through SEL_3 (Process, Scaling, Tuning)

Input values for the selector.

SEL_TYPE (Scaling)

Defines the selector action—High, Medium, or Low.

SET_FSTATE (Faultstate, Option)

Allows the user to set the device faultstate to active. This, in turn, forces all
output blocks into their own faultstate behavior.

Table 4-20. Device States

State

Meaning

Start/Restart

The device has just started a restart cycle.

Initialization

The device is performing startup diagnostics.

Failure

A hardware failure has been detected.

On-Line Linking

The device is online and waiting for new parameter linkages to be
established.

On-Line

The device is online and in service.

Standby

The device is online, but currently out of service.