Troubleshooting and Common Questions

NI-FBUS Configurator User Manual

B-16

ni.com

Using Fieldbus with Lookout

How do I use Fieldbus with Lookout?

1.

In Lookout, create an

OPCClient

object. Edit connections for this

OPCclient

object and set the

Activate

member to

FALSE

.

2.

Add all the items you are interested in.

3.

Activate the

OPCclient

object by going through Edit Connections

dialog box and setting the

Activate

member to

TRUE

. This will

configure the MVC items.

4.

To open a previously saved lkp/process file, follow a similar
deactivation/activation procedure.

What do I do if Fieldbus objects do not appear in Lookout?

If you want to use the native Fieldbus objects in Lookout, you have to delete
the

lookout.dat

file in the Lookout directory. This file is an index file

that tells Lookout what objects it has available. Fieldbus objects are not
available by default. Lookout will regenerate the

lookout.dat

file the

next time it is started. When it regenerates the file, it will see that Fieldbus
software has been installed and will make the Fieldbus objects available.

How do I use Fieldbus Alarms in Lookout?

In Lookout, there is a separate alarms window for Fieldbus alarms. Under
the Options menu, choose Fieldbus to show this window. The window can
also be shown using traditional Lookout datamember

ShowAlarms

. Refer

to the entry for National Instruments Fieldbus in the Lookout object
reference manual (also available from the Help menu within Lookout).

Note that if you want alarms to appear in the standard Lookout alarm
window (rather than the Fieldbus alarms window), you must create
Lookout alarm objects.

I am trying to control a PID loop within the FP-3000. On occasion, the
Lookout operator may want to override the output of the PID with a
manual output setpoint. How can I implement this?

1.

Double-click your PID block in the NI-FBUS Configurator.

2.

Under the Options tab, you will see a parameter called

CONTROL_OPTS

. There are several options that you can enable or

disable. When you click to the right of the parameter name, a drop box
appears. Check the box next to

TRACK ENABLE

. This gives you the