SHED_OPT (Mode Shedding, Option)

Controls the way blocks enter mode shedding. Each option listed below has
a companion

No Return

option. The

No Return

shedding options change

the target mode of the device to the shed mode and prevent the device from
re-entering

RCas

or

ROut

mode after the shed condition has ended.

SHED_RCAS (Mode Shedding)

The shed time for the

RCAS_IN

parameter. If the block is in

RCas

mode and

the

RCAS_IN

parameter has not been updated in

SHED_RCAS

time, the

block performs mode shedding as determined by the

SHED_OPT

parameter.

SHED_ROUT (Mode Shedding)

The shed time for the

ROUT_IN

parameter. If the block is in

RCas

mode and

the

ROUT_IN

parameter has not been updated in

SHED_RCAS

time, the

block performs mode shedding as determined by the

SHED_OPT

parameter.

SIMULATE (Option)

Used to bypass the physical I/O channel and allow the block to operate
normally, using a simulated I/O channel.

Note

For this feature to be enabled on an FP-3000, you must set a switch on the back of

the device. To see how to configure the switch, refer to the FP-3000 manual.

SIMULATE_D (Option)

Used to bypass the physical I/O channel and allow the block to operate
normally, using a simulated discrete I/O channel.

Table 4-21. Shed Conditions

Shed Mode

Behavior

Normal Shed

The block sheds into the next higher-priority mode set in the permitted
mode field of

MODE_BLK

.

Shed to Auto

The block sheds into automatic mode.

Shed to Manual

The block sheds into manual mode.

Shed to Retained

The block sheds to the next higher priority mode set in the target mode
field of

MODE_BLK

.