Scaling Parameters

The scaling parameters differ depending on the type of function block.
For example, scaling on an AI will be different from scaling on an DI.
For an Analog Input (AI) block, the most important scaling parameters are
as follows.

L_TYPE

—The linearization type used in taking the physical transducer

value to the block output.

XD_SCALE

—Used to take values from the physical transducer for the

I/O channel to a percent of scale. This percent of scale value is called

FIELD_VAL

.

OUT_SCALE

—Used in combination with

L_TYPE

to take the percent of

scale to an output value. This output value is called

OUT

.

The following diagrams will assist you in determining the parameters you
need to change to obtain the correct scaling for AI, AO, or PID blocks. Each
box indicates the application of the parameter it contains.

Table 4-3. Faultstate Parameters

CLR_FSTATE

FSTATE_VAL_D

FAULT_STATE

SET_FSTATE

FSTATE_TIME

STATUS_OPTS

FSTATE_VAL