Cascade and Remote Cascade
Setups

Cascade Initalization

Foundation Fieldbus provides a protocol called Cascade Initialization that
allows a control function block to smoothly transition from

Man

to

Auto

mode. Cascade Initialization allows the PID algorithm to know the current
setpoint of the AO block to balance the actual setpoint with the control
setpoint over time. Cascade Initialization is also used to prevent windup in
the PID.

Parameter Connections for Cascade Initialization

Cascade initialization takes place between two blocks: an upstream
controlling block, and a downstream controlled block. In a PID loop,
the upstream block is the PID block, and the downstream block is the
AO block. In the case of cascaded PID blocks, the upstream PID feeds a
setpoint into a second PID that is acting as the downstream block. In both
cases, the parameter connections are the same. The output (

OUT

) parameter

of the upstream block is connected to the cascade input (

CAS_IN

)

parameter of the downstream block. This connection controls the setpoint
of the downstream block. To allow the upstream block to determine the
current setpoint of the downstream block, you must also connect the
backward calculation output (

BKCAL_OUT

) parameter of the downstream

block with the backward calculation input (

BKCAL_IN

) of the upstream

block. The connections are shown in the following figure.