Symptom

Possible Cause

Corrective Action

Convection blower fails to

start.

#1 snap disc defective.

Blower not plugged in.

Blower is defective.

Control box is defective.

Replace snap disc.

Check that blower is plugged into wire har-

ness.

Replace blower.

Replace control box.

Exhaust blower fails to

start or does not shut off.

Blower not plugged in.

Blower is clogged with ash.

Blower is defective.

Control box is defective.

Check that blower is plugged into wire har-

ness.

Clean exhaust system.

Replace blower.

Replace control box.

Large, lazy fl ame, orange

color. Black ash on glass.

Dirty appliance.

Poor fuel quality, high ash content.

Firepot clean-out plate not completely

closed.

Excessive amount of fuel.

Clean appliance, including fi repot, heat

exchangers and venting system. Remove

stainless steel baffl e from fi rebox to clean

ash from on top of baffl e. Clean behind rear

brick panels. Change fuel brand to pre-

mium.

Check that fi repot clean-out plate is fully

closed.

Reduce feed rate using feed rate adjustment

control rod located inside hopper.

Nuisance shutdowns.

Low fl ame.

Sawdust buildup in hopper.

Feed motor is reversing.

Defective thermocouple.

Defective control box
Firepot more than 1/2 full

Increase feed by opening feed rate adjust-

ment control rod located inside hopper.

Clean hopper, see

page 35.

Check for good connections between feed

motor and wire harness.

Replace thermocouple.

Replace control box.
See

page 36 for detailed instructions for

“High Ash Fuel Content Maintenance”

Appliance calls for heat.

Call light illuminates.

Exhaust blower starts.

No feed or igniter.

Thermocouple is defective or not properly

plugged in.

Defective control box

Check connections on thermocouple or

replace if defective.

A fl ashing yellow light on the control box

indicates a problem with the thermocouple.

Replace control box.

Hopper lid not closed all

the way

Switch or magnet is out of adjustment

(auger will not function)

Close the lid. If that doesn’t work, adjust or

replace the switch or magnet