JKSSS+ Series - 94

JKSSS+ Series

2.3 - 4.2KV

7.8 - Instructions for Low Voltage Test

Tools:

• Phillips screwdriver

• Medium voltage fuse pullers if available

• Two control power transformer (Test PT) 500 VA minimum

• 120Vac control power (Test plug)

• Low voltage motor strapped for the proper voltage (typically 5 HP or

less)

• Oscilloscope if available

• Wire jumper

• Test switch (single pole i.e. - light switch)

• Manual (reference drawing above)

Procedure:

1. Verify that no DC or AC voltage

is present on any of the power

components.

2. Verify setup of control power

transformers for the proper

voltage. If using 480Vac or 240Vac 3 phase verify transformers are

strapped for that voltage. See above drawing. Configure as an open

delta for 3 phase as shown in drawing.

3. Verify medium voltage disconnect is open and pull medium voltage

fuses including PT and CPT fuses.

4. Connect 3 phase power 480 or 240Vac to the down stream side of

the fuses. Do not connect to disconnect side of fuses. Depending on

the small test motor used will depend on what size cable or current

that is required. Also, connect the Primaries of the TEST PT in the

proper phase sequence of A-B-C.

5. Disconnect medium voltage motor.

6. Connect low voltage motor. (Typically 5 HP or less)

7. Connect a wire jumper between TB8 pins 1 and 2 on the TCB (con-

trol board) to bypass fuse blown and open disconnect fault. The

TCB is located in the low voltage compartment.

8. Install a switch on TB1 pins 1 and 8 on the TCB (control board) to

bypass all interlocks (TEST Switch).

DANGER

HAZARDOUS VOLTAGE

Disconnect all power supplying this equipment prior
to working on it.

Failure to follow this instruction will result in death
or serious injury.

DANGER

HAZARDOUS VOLTAGE

Remove all medium voltage fuses to prevent back-
feeding transformers.

Failure to follow this instruction will result in death
or serious injury.

Construct an open delta low

voltage source for powering

the MVC for low voltage testing

(Minimum of 500VA each)

Connect to MVC3-MB (Main Firing Board)

Caution: Remove the three phase transformer PT fuses and CPT fuses

on panel to prevent backfeed to the Medium Voltage

Ensure proper

phase sequence

PTs

TB1 Terminal 1

Low Voltage Panel

TB1 Terminal 3

TB1 Terminal 5

120 VAC 3 Phase Output

H2

H2

X2

X2

X1

X1

H1

H1

B

C

A

B

C

A

480 or 240 VAC 3 Phase Supply