SP.6 User I/O Configuration (Setpoint Page 6)

(Security Level: 2)

SP6.5 User Programmable External Inputs: The

controller provides up to 4 digital external inputs

which are individually programmable. A description

name can be assigned to each individual input for

easy identification.

External Input #1: Factory programmed for TCB

Trip.

• External Input #2: If used, this setpoint must be

enabled.

• Name Ext. Input #2: The user can assign a

description name to the input to easily identify

the cause of external trip or alarm. Up to 15

characters including spaces can be used to assign

the name.

• External Input #2 Type: The external input can

be set as either a normally open or normally

closed contact.

• External Input #2 Time Delay: Upon a change in

contact setting, the unit will wait the programmed

amount of time before generating an output. If

no delay is needed, then input 0 seconds. The

controller will post an event upon seeing a change

in state.

• External Input #3: The setup screens and

setpoints for External Input #3 includes the option

of being configured for Dual Ramp. In Dual Ramp

mode, the initial contact setting is the same as the

START RAMP #1. Upon a change in input contact

state, the controller will switch over to START

RAMP #2 and use that setting for start control

mode. Note: The start RAMP types should only be

switched while the motor is stopped. In Setpoint

Page 4 Relay Assignments, do not assign any

output relay to this function. The controller will

ship with External input #3 programmed for dual

ramp. If it is not needed, disable the dual ramp.

• External Input #4: This input screens are for the

thermostat input and can be enabled or disabled.

Note: It is recommended that this function remain

enabled. If the thermostat indicates an over

temperature condition, the controller will trip the

motor.

USER
PROGRAMMABLE
EXTERNAL
INPUTS
(Continued)

TCB FAULT
SELECT: ENABLED

NAME EXT. INPUT #1
TCB FAULT

Options: Enabled or Disabled

See text for directions

EXTERNAL INPUT #2
SELECT: DISABLED

NAME EXT INPUT #2

Options: Enabled or Disabled

See text for directions

DUAL RAMP
SELECT: DUAL RAMP

NAME EXT INPUT #3
SECOND RAMP

Options: Enabled, Disabled or

Dual Ramp

See text for directions

THERMOSTAT
SELECT: ENABLED

NAME EXT INPUT #4
THERMOSTAT

Options: Enabled or Disabled

See text for directions

TCB FAULT
TYPE: NORMALLY OPEN

Options: Normally Open or

Normally Closed

EXTERNAL INPUT #2
TYPE: NORMALLY OPEN

Options: Normally Open or

Normally Closed

DUAL RAMP
TYPE: NORMALLY OPEN

Options: Normally Open or

Normally Closed

THERMOSTAT
TYPE: NORMALLY CLOSED

Options: Normally Open or

Normally Closed

TCB FAULT
TIME DELAY: 1 SEC.

Range: 0 - 60 SEC
Increments of 1

EXTERNAL INPUT #2
TIME DELAY: 0 SEC.

Range: 0 - 60 SEC.
Increments of 1

DUAL RAMP
TIME DELAY: 0 SEC.

Range: 0 - 60 SEC
Increments of 1

THERMOSTAT
TIME DELAY: 1 SEC.

Range: 0 - 60 SEC.
Increments of 1