JKSSS+ Series - 61

JKSSS+ Series

2.3 - 4.2KV

SP.7 Custom Acceleration Curve (Setpoint Page 7)

(Security Level: 3)

SP7.1 Setpoint Page 7 allows the user to custom design

the acceleration curve (start curve) to the specific

application. The user can custom design up to

three different curves in the soft starter. Only one

curve can be active (enabled) at a time. Each of

the three curves has eight voltage levels, with

corresponding ramp times and a current limit

setting.

Note: Each successive voltage level must be

programmed to a voltage level equal to or greater

than the previous level. All eight levels of voltages

must be programmed and the eighth level has

been preset at 100%.

If Custom Accel Curve has been set to curve A, B

or C on this page, the soft starter will override the

Start Control Mode selected in Setpoint Page 2,

(even if Start Control Mode in Setpoint Page 2 has

not been set to Custom Accel Curve).

Note: Setpoint Page 7 has a security level 3

requirement.

CURVE C VOLTAGE
LEVEL 6: 67%

CURVE C VOLTAGE
LEVEL 7: 82%

CURVE C RAMP
TIME 7: 2 SEC.

CURVE C VOLTAGE
LEVEL 8: 100%

CURVE C RAMP
TIME 6: 2 SEC.

CURVE C CURRENT
LIMIT: 350% FLA

CURVE C RAMP
TIME 8: 2 SEC.

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 200 - 600%
Increments of 10

CUSTOM CURVE C