Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 23

Advertising
background image

JKSSS+ Series - 17

JKSSS+ Series

2.3 - 4.2KV

Ensure that safety signs are not covered or obscured by paint.

Do not remove, cover or destroy any safety signs.

The setting of any adjustable current and voltage trip mechanisms should be verified to

the proper values.

NOTE: Damage from faults can be reduced if devices used for short circuit and ground

fault protection are chosen and set to operate at values as close to minimum as feasible,

while allowing normal transients.

All switches, relays and other operating mechanisms should be manually exercised to

make certain that they are properly aligned and operate freely.

Operating mechanisms such as interlocks, key switches, etc. should be checked for func-

tion as intended for protection of personnel and equipment.

Overload relay settings should be checked to be sure they are selected and adjusted to

the proper settings per the load nameplate data.

Power circuit fuses were selected and installed in accordance with the application re-

quirements. Fuses must be completely inserted in their holders. Instruction on removing

and installing the fuses can be found in one of the following manuals: VF010H03 (Fixed

Type) or VF010H01 (Drawout Type).

Electrical Checks

With incoming power isolated and all loads disconnected electrically, the control cir-

cuit and other mechanisms should be exercised to determine that the devices operate

properly. An auxiliary source of control power will be necessary to provide power to the

electrical operators.

Electrical shock hazard. Do not touch energized components

during a test using auxiliary power.

The ground fault protection system (if furnished) should be tested in accordance with the

instructions furnished with the device.

An electrical insulation test should be performed to ensure that the controller and asso-

ciated field wiring are free from short circuits and grounds. The preferred method is to

perform a dielectric test at 2.25 times the nominal system voltage plus 2000 volts. This

should be done phase-to-ground, phase-to-phase and phase-to-neutral (if applicable),

with all switches and circuit breakers opened. Disconnect any devices which may have

limited dielectric strength and that are not intended for this test.

The light or buzzer, or both, used to indicate breakdown should be calibrated to indicate

failure with an output current between 1.5 and 2.0 milliamperes per 1000 volts applied.

Hazardous voltages are present during dielectric testing

which can result in serious injury or death. High potential

tests should be performed only by qualified personnel.

Refer to safety instructions provided with the test equipment.

All devices must be set to their normal or OFF position before energizing incoming power.

WARNING

WARNING

WARNING

Advertising