JKSSS+ Series - 64

JKSSS+ Series

2.3 - 4.2KV

SP.9 RTD Configuration (Setpoint Page 9)

(Security Level: 3)

The soft starter comes with an RTD card that provides 12

programmable RTDs which are individually programmable

for type. The available types are 100 ohm platinum, 100 ohm

nickel, 120 ohm nickel and 10 ohm copper. Each RTD can

be identified with a description name of up to 15 characters

(including spacing). Also, each individual RTD has it own alarm

and trip level.

SP9.1 Use NEMA Temp for RTD Value: When this setpoint

is enabled, the soft starter will use the NEMA design

insulation class to limit the maximum allowed range

of the alarm and trip level. The maximum allowed

temperature range is 240° C or (464°F).

SP9.2 # Of RTD’S Used for Stator: Up to six RTDs can be

assigned to monitor the stator of the motor.

SP9.3 RTD Voting: When this is enabled, the soft starter will not

post a trip until 2 RTD’s have exceeded the trip level.

This prevents nuisance RTD tripping.

SP9.4 All 12 RTDs are configured in the following manner. The

first column is the RTD type, the second column is the

RTD description, the third column is the alarm level,

and the fourth column is the trip level.

The first six RTDs have been pre-programmed with

a description name for the STATOR, with two RTDs

per phase. RTDs #1 & #2 have been named STATOR

PHASE A1 and A2 respectively. RTDs #3 & 4 are

named STATOR PHASE B1 and B2, RTDs #5 & 6

are named STATOR PHASE C1 and C2. If other

description names are required, press the right arrow

button from the RTD Type screen to go the RTD

description screen. If no alarm or trip level is required

these setpoints can be turned off.