Chapter 7 - maintenance and troubleshooting, Jksss+ series 2.3 - 4.2kv, 1 - failure analysis – Toshiba VF010H05 User Manual

Page 86

Advertising
background image

JKSSS+ Series - 80

JKSSS+ Series

2.3 - 4.2KV

Chapter 7 - Maintenance and Troubleshooting

The soft starter is designed to be a maintenance-free product. However, as with all electronic equipment, the

unit should be checked periodically for dirt, moisture or industrial contaminants. These can cause high voltage

arc-over, carbon tracking or prevent proper cooling of the SCR heat sinks. All bolts should be checked annu-

ally for proper tightness using an accurate torque wrench. According to the manufacturer’s manual, check the

contactor for air gap spacing of the vacuum bottles.

Note: If the unit is installed in a contaminated environment and forced air cooling is used, blower

filters must be checked and cleaned regularly to insure proper air flow and cooling of the enclosure.

7.1 - Failure Analysis

When a fault occurs, the LCD will display the fault error and the listed LED and AUX Relay will be lit.

Please clear all faults before attempting to restart the unit. Note: If the problem persists after the

required programming changes have been made, and all corrective action has been taken, please

contact the factory for assistance.

Problem

CPU LCD Display

LED

Aux

Relay

Possible Cause

Solutions

Short circuit between the

inputs

Locate and remove short

Faulty SCRs

Remove power and test SCR(s). Refer to
Section 7.1.1 for the SCR testing
procedure

Short circuit or ground fault

in motor/cabling

Locate and remove short or ground

Phase Loss

Repair cause of phase loss

Branch circuit protection

not correctly sized

Verify correct sizing of branch circuit
protection

Faulty main circuit board

Remove power and replace main circuit
board.

Faulty SCRs

Remove power and test SCR(s). Refer to
Section 7.1.1 for the SCR testing
procedure

Single phase incoming

power

Correct problem with incoming power

Faulty SCRs

Remove power and test SCR(s). Refer to
Section 7.1.1 for the SCR testing
procedure

Fan(s) not functioning

(If supplied)

If fans have power, remove power and
replace fan(s). If fans do not have power,
find cause of power loss and repair.

Heatsink coated with dirt

Remove power and clean heatsink with
high pressure air (80 - 100 psi max clean
and dry air)

Overcurrent on unit

Verify that running current does not
exceed unit rating

Environment temperature

over 122° F (ambient

temperature for chassis

units) or over 104°F

(ambient temperature for

enclosed version

Place unit in environment temperature
less than 122°F for panel version or less
than 104°F for enclosed version.

Bypass failed to close

Check bypass contactor and wiring

AUX1

AUX1

Thermostat trips

during run

EXTERNAL TRIP ON

THERMOSTAT

Trip

AUX1

Short Circuit Trip

SHORT CIRCUIT TRIP

Single Phase Trip

SINGLE PHASE TRIP

(Check LCD display for

possible fault indicators)

One of the main

fuses blows or

circuit breaker

opens when the

power is applied

or disconnect is

open

TCB FAULT TRIP

Trip

AUX1

Trip

Trip