Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 58

Advertising
background image

JKSSS+ Series - 52

JKSSS+ Series

2.3 - 4.2KV

SP3.12 Overvoltage Trip Level: Typically used to indicate

that the line voltage is too high and at which point a

trip occurs

• Overvoltage Trip Delay: The amount of time that

the overvoltage condition must exist before a trip

will occur.

SP3.13 Undervoltage Alarm Level: Typically used to

indicate when the line voltage is too low. This is an

alarm level.

• Undervoltage Alarm Delay: The amount of time

that the overvoltage condition must exist before a

trip will occur.

SP3.14 Undervoltage Trip Level: Typically used to

indicate that the line voltage is too low and at which

point a trip occurs

• Undervoltage Trip Delay: The amount of time that

the undervoltage condition must exist before a trip

will occur.

SP3.15 Line Frequency Trip Window: The acceptable

amount of drift above or below the line frequency

(Hz) before a trip is generated.

• Line Frequency Trip Delay: The amount of time

that the frequency drift condition must exist beyond

the window before a trip will occur.

SP3.16 Power Factor Lead Alarm: Typically used to

indicate a leading power factor.

• Power Factor Lead Alarm Delay: The amount of

time that the power factor lead condition must exist

beyond the window before a trip will occur.

SP3.17 Power Factor Lead Trip: The acceptable amount

of power factor lead before a trip is generated.

• Power Factor Lead Delay: The amount of time

that the power factor lead condition must exist

beyond the window before a trip will occur.

SP3.18 Power Factor Lag Alarm: Typically used to

indicate a lagging power factor.

• Power Factor Lag Alarm Delay: The amount of

time that the power factor lagging condition must

exist beyond the window before a trip will occur.

SP3.19 Power Factor Lag Trip: The acceptable amount

of power factor lag before a trip is generated.

• Power Factor Lag Delay: The amount of time

that the power factor lag condition must exist

beyond the window before a trip will occur.

SP3.20 Power Demand Period: The soft starter

measures the demand of the motor for several

parameters (current, kW, kvar, kVA). The demand

values of motors assists in energy management

programs where processes may be altered or

scheduled to reduce overall demand. Demand

is calculated by a programmed amount of time

where current, kW, kvar and kva samples are

taken and then averaged and stored to assess

demand.

Advertising