Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 63

Advertising
background image

JKSSS+ Series - 57

JKSSS+ Series

2.3 - 4.2KV

SP.6 User I/O Configuration (Setpoint Page 6)

(Security Level: 2)

The controller can be configured to accept a tachometer

feedback signal through the 4-20mA input.

SP6.1 The first screen of setpoint page 6 is TACHOMETER

SCALE SELECTION. When this is set to

ENABLED, the user will need to input the

tachometer scale of the 4-20mA input range.

• Manual Tach Scale 4.0 mA: The unit is looking

for an RPM value to assign to the lowest point on

the scale. This value should represent the motor

at zero speed.

• Manual Tach Scale 20.0 mA: The unit is looking

for an RPM value to assign to the highest point on

the scale. This value should represent the motor

at full speed.

SP6.2 Tach Accel Trip Mode Select: When enabled, the

underspeed or overspeed must be selected for the

Tach Accel Trip. If underspeed is selected, only

the Tach Underspeed Trip Point will be used. If

overspeed is selected only the Tach Overspeed

Trip Point will be used.

• Tach Ramp Time: This is the duration of time

before the tachometer begins to sample.

• Tach Underspeed Trip: The minimum value of

motor RPM which must be achieved before the

Tach Ramp Time sample is taken.

• Tach Overspeed Trip: The maximum motor RPM

allowed when the Tach Ramp Time sample is

taken.

• Tach Accel Trip Delay: The duration of time that

the Tach Accel trip condition must persist before a

trip is generated.

SP6.3 The controller provides two 4-20mA analog outputs.

Each analog output is independent of the

other and can be assigned to monitor different

functions. The available output ranges are RPM,

Hottest Non-Stator (Bearing) RTD, Hottest Stator

RTD, RMS current, % Motor Load, or kW.

• Analog Output #1 – Select a function from

the available options to be transmitted from

the 4-20mA output. Note: If selecting RPM,

the Tachometer feedback input signal must be

present in order for the controller to give proper

output. If selecting RTD, the RTD option must

be installed and an RTD input signal must be

present for a proper output to be given from the

analog output.

• Analog Output #1 (4 mA): Enter a value that the

4mA level will represent for the selected function;

typically this value should be 0.

• Analog Output #1 (20 mA): Enter a value that

the 20mA level will represent for the selected

function.

SP6.4 Analog Output #2 – All of the setpoints and setup

screens for Analog Output #2 are the same as

those for Analog Output #1.

Advertising