Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 47

Advertising
background image

JKSSS+ Series - 41

JKSSS+ Series

2.3 - 4.2KV

5.1.7 Custom Acceleration Curve (Setpoint Page 7)

5.1.8 Overload Curve Configuration (Setpoint Page 8)

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Custom Accel Curve

Disabled

Disabled, Curve A, B, or C

Custom Curve A

Curve A Voltage Level 1

25%

0-100%

Curve A Ramp Time 1

2 sec

1-60 sec

Curve A Voltage Level 2

30%

0-100%

Curve A Ramp Time 2

2 sec

1-60 sec

Curve A Voltage Level 3

37%

0-100%

Curve A Ramp Time 3

2 sec

1-60 sec

Curve A Voltage Level 4

45%

0-100%

Curve A Ramp Time 4

2 sec

1-60 sec

Curve A Voltage Level 5

55%

0-100%

Curve A Ramp Time 5

2 sec

1-60 sec

Curve A Voltage Level 6

67%

0-100%

Curve A Ramp Time 6

2 sec

1-60 sec

Curve A Voltage Level 7

82%

0-100%

Curve A Ramp Time 7

2 sec

1-60 sec

Curve A Voltage Level 8

100%

0-100%

Curve A Ramp Time 8

2 sec

1-60 sec

Curve A Current Limit

350% FLA

200-500%

Custom Curve B

Same Programmable Data Points and Ranges
as Custom Curve A

Custom Curve C

Same Programmable Data Points and Ranges
as Custom Curve A

Page

7

Custom Acceleration Curve

Level

3

Password Protection

SP7.1

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Basic Run Overload Curve

Run Curve Locked Rotor Time

O/L Class

1-30 sec, O/L Class

Run Locked Rotor Current

600% FLA

400-800%

Coast Down Timer

Disabled

1-60 Min, Disabled

Basic Start Overload Curve

Start Curve Locked Rotor Time

O/L Class

1-30 sec, O/L Class

Start Locked Rotor Current

600% FLA

400-800%

Acceleration Time Limit

30 sec

1-300 sec, Disabled

Number of Starts Per Hour

Disabled

1-6, Disabled

Time Between Starts Time

5 min

1-60 Min, Disabled

Area Under Curve Protection

Disabled

Enabled or Disabled

Max I*I*T Start

368 FLA

1-2500 FLA*FLA*sec

Current Over Curve

Disabled

Disabled, Learn, Enabled

Learned Start Curve Bias

10%

5-40%

Time for Sampling

30 sec

1-300 sec

Level

3

Password Protection

Page

8

Overload Curve Configuratio

n

SP8.1

SP8.2

SP8.3

SP8.4

Advertising