JKSSS+ Series - 67

JKSSS+ Series

2.3 - 4.2KV

SP.12 System Setpoints (Setpoint Page 12)

(Security Level: 3)

MENU

PAGE 12 SYSTEM
SETPOINTS

DEFAULT DISPLAY
SCREEN

(Hit DOWN ARROW eleven times)

METERING DATA
PAGE #: 1

Enter Metering Page (1 - 4)
Number for display

METERING DATA
SCREEN #: 1

ALARMS

THERMAL REGISTER
SETUP INFORMATION

PRESS ENTER TO CLR
THERMAL REGISTER

RTD FAILURE ALARM
ALARM: DISABLED

THERMAL REGISTER
ALARM: 90%

HOT STALL TIME
: 1/2 O/L CLASS

STOPPED COOL DOWN
TIME: 30 MIN

RUNNING COOL DOWN
TIME: 15 MIN

COLD STALL TIME
: O/L CLASS

RELAY MEASURED COOL
RATES: DISABLED

Enabled or Disabled

Range: Off, 40 - 95%
Increments of 1

Range: O/L CLASS,
4 - 40 SEC

Increments of 1

Range: 1/2 O/L CLASS,
4 - 40 SEC
Increments of 1

Range: 10 - 300 MIN
Increments of 1

Range: 10 - 300 MIN
Increments of 1

Range: ENABLED or
DISABLED

THERMAL ALARM
DELAY: 10 SEC.

Range: 1 - 20 SEC.
Increments of 1

Enter Metering
Screen Number for display

MOTOR DESIGN AMBIENT
TEMPERATURE: 40 C

MOTOR DESIGN RUN
TEMPERATURE: 80% MAX

MOTOR STATOR MAX
TEMPERATURE: INS CLS

THERMAL REGISTER
MINIMUM: 15%

I/B INPUT TO THERMAL
REGISTER: ENABLED

Range: 10 - 50%, OFF
Increments of 1

Range: 10 - 90 C
Increments of 1

Range: 50 - 100% of Motor
Stator Max Temp.
Increments of 1%

Range: Insulation Class
10 - 240 C
Increments of 1

Options: ENABLED or
DISABLED

USE CALCULATED K OR
ASSIGN: 7

Range: 1 - 50, ON