Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual

Page 61

Advertising
background image

JKSSS+ Series - 55

JKSSS+ Series

2.3 - 4.2KV

SP.5 Relay Configuration (Setpoint Page 5)

(Security Level: 2)

In Setpoint Page 5 the user

can configure the four output

relays as either fail-safe or

non fail-safe and latching or

non-latching.

SP5.1 When a relay has been configured

as fail-safe and power is applied,

the relay will be energized. The

relay will then de-energize when

an event occurs or if the power

fails. Note: The relays in the

soft starter will not prevent a start

sequence unless they are wired in

as interlocks. If power is lost, the

motor power is also lost. Do not

change the programming for AUX

1-4. These are for factory use only.

AUX 5-8 are user defined outputs.

SP5.2 A relay configured as non-latching

will reset itself when the cause of

the trip event is not continuous.

The TRIP (AUX1) relay should

always be programmed for latching,

because this trip should require a

visual inspection of the motor and

starter before issuing a manual

reset to release the relay after a trip

has been stored.

PAGE 5 RELAY
CONFIGURATION

TRIP (AUX1) RELAY
FAIL-SAFE: NO

Options: Yes or No

(Hit DOWN ARROW four times)

TRIP (AUX1) RELAY
LATCHED: YES

ALARM (AUX2) RELAY
FAIL-SAFE: NO

AUX4 RELAY
FAIL-SAFE: NO

ALARM (AUX2) RELAY
LATCHED: NO

AUX4 RELAY
LATCHED: NO

AUX5 RELAY
FAIL-SAFE: NO

AUX6 RELAY
FAIL-SAFE: NO

AUX5 RELAY
LATCHED: NO

AUX6 RELAY
LATCHED: NO

AUX 3 RELAY
FAIL-SAFE: NO

AUX3 RELAY
LATCHED: NO

AUX7 RELAY
FAIL-SAFE: NO

AUX7 RELAY
LATCHED: NO

AUX8 RELAY
FAIL-SAFE: NO

AUX8 RELAY
LATCHED: NO