Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 50

Advertising
background image

JKSSS+ Series - 44

JKSSS+ Series

2.3 - 4.2KV

5.1.12 System (Setpoint Page 12)

5.1.13 Calibration and Service (Setpoint Page 13)

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Default Display Screen

Metering Data Page #

1

Enter Metering Page (1-4)

Metering Data Screen #

1

Enter Metering Screen
Page 1(1-10)
Page 2 (1-11)
Page 3 (1 - 29)
Page 4 (1 - 6)

Alarms

RTD Failure Alarm

Disabled

Enabled or Disabled

Thermal Register Alarm

90%

Off, 40-95%

Thermal Alarm Delay

10 sec

1-20 sec

Thermal Register Setup Info

Cold Stall Time

O/L Class

O/L Class (5-30) or 4-40 second time delay

Hot Stall Time

½ O/L Class

½ O/L Class, 4-40 sec

Stopped Cool Down Time

30 Min

10-300 Min

Runing Cool Down Time

15 Min

10-300 Min

Relay Measured Cool Rates

Disabled

Enabled or Disabled

Thermal Register Minimum

15%

10-50%

Motor Design Ambient Temp

40C

10-90C

Motor Design Run Temperature

80% Max

50-100% of Motor Stator Max Temp

Motor Stator Max Temp

INS CLS

INS CLS, 10-240 C

I/B Input to Thermal Register

Enabled

Enabled or Disabled

Use Calculated K or Assign

7

1-50, On

Press Enter to Clr Thermal Register

SP12.4

Page 12

System Setpoint

s

Level

3

Password Protection

SP12.2

SP12.3

SP12.1

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Set Date and Time
(DDMMYY:HHMM)

FACTORY SET;
##/##/## ##:##

Enter Date (DDMMYYYY)

FACTORY SET;
##/##/####

D=1-31, M=1-12, Y=1970-2069

Enter Time (HH:MM)

FACTORY SET;
##:##

H=00-23, M=0-59

Model #
Firmware REV. #

FACTORY SET;
###### ######

Display Only, Cannot be changed

SP13.2

Press Enter to Access Factory
Settings

Available to Qualified Factory Personnel

SP13.3

Page 13

Calibration & Service

FACTORY USE ONLY

SP13.1