Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 87

Advertising
background image

JKSSS+ Series - 81

JKSSS+ Series

2.3 - 4.2KV

Proble m

CPU LCD Displa y

LED

Aux

Re la y

Possible Ca use

Solutions

Los s of 1 or m ore

phas es of power from

utility or generated pow er

Check power s ource

Blown power fus es

Check for s hort circuits

Im proper program m ing

Check m otor nam eplate vers us
program m ed param eters

Pos s ible load dam age or

jam m ed load

Check m otor currents

Im proper s etting for

m otor load condition

Verify current lim it s etting

Dam aged load

Check for load failure

Im proper program m ing

Check s etpoint s ettings

Wrong pos ition of

dis connected breaker

Check dis connect or open breaker

Main contactor failed to

clos e

Check internal connections

Trans form er too s m all

Reduce current lim it s etting, s aturation
or s agging power s upply trans form er

Im proper program m ing Check s etpoint s ettings

U nloaded m otor

Check load

Failed C PU or Main Firing

Board

Contact factory

Vibration

Check internal w iring connections

Troubles hoot and repair generator

Contact utilities com pany

Main board failure

Three phas e power rem oved from
Main Board

Im proper program m ing

Check program s etpoints

Any w ire going to ground
(I.e. s tator ground, m otor

ground, s oft s tart ground)

Check with m egger or Hi-pot m otor
leads and m otor

High vibration or loos e

connections

Check internal connections

Load s horted/ grounded/

faulted

Rem ove power and repair.

Faulty m ain circuit board Replace the m ain circuit board

Short in control circuit

Rem ove power, locate and rem ove
this s hort

Wrong control voltage

Apply the correct voltage to the control
circuit

UNDER CURRENT TRIP

Trip

AUX1

AU X1

Any Ground

Fault Trip

GROUND FAULT

HI-SET OR LO-SET

Trip

Under Voltage

Trip

UNDER VOLTAGE TRIP

Trip

AUX1

Overload

OVERLOAD TRIP

Trip

AU X1

Phase Loss

PHASE LOSS

Trip

AU X1

Stall prevention

ACCEL TIME TRIP

Trip

AUX1

Generator Pow er

Problem or grid change

AUX1

Self-test Failure

SELF-TEST FAILURE

Trip

Line Frequency

Trip

OVER OR UNDER

FREQUENCY TRIP

Trip

AUX1

Under Current

Trip

W arning: This is a s erious fault condition. Ens ure that the fault
condition is cleared on the load before attem pting to res tart the
m otor.

Control circuit

fuses b low after
control power is

applied.

None

None

None

Motor stopped

during run

Check for fault indication

Trip

AU X1