Chapter 5 - setpoint programming, Jksss+ series 2.3 - 4.2kv, 1 setpoints page list – Toshiba VF010H05 User Manual

Page 42

Advertising
background image

JKSSS+ Series - 36

JKSSS+ Series

2.3 - 4.2KV

5.1 Setpoints Page List

These charts list the Setpoint Page, the programmable functions and the section.

5.1.1 Basic Configuration (Setpoint Page1)

5.1.2 Starter Configuration (Setpoint Page 2)

Chapter 5 - Setpoint Programming

The JKSSS+ Series has thirteen programmable setpoint pages which define the

motor data, ramp curves, protection, I/O configuration and communications. In Section

5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages

are illustrated and defined for easy navigation and programming. Note: Setpoints can

only be changed when the starter is in the Ready Mode. Also the soft start will not start

when it is in programming mode.

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Start Control Mode

Start Ramp 1

Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp

SP2.1

Jog Voltage

50%

5-75%, Off

SP2.2

Start Ramp #1 Type

Voltage

Current, Voltage

Initial Voltage #1

20%

0-100%

Ramp Time #1

10 sec

0-120 sec

Current Limit #1

350% FLA

200-500 %

Initial Current #1

200% FLA

0-300%

Ramp Time #1

10 sec

0-120 sec

Maximum Current #1

350% FLA

200-500 %

Start Ramp #2 Type

Disabled

Current, Voltage, Disabled

Initial Voltage #2

60%

0-100 %

Ramp Time #2

10 sec

0-120 sec

Current Limit #2

350 % FLA

200-500 %

Initial Current #2

200% FLA

0-600 %

Ramp Time #2

10 sec

0-120 sec

Maximum Current #2

350% FLA

200-500 %

Kick Start Type

Disabled

Voltage or Disabled

Kick Start Voltage

65%

10-100 %

Kick Start Time

0.50 sec

0.10-2.00

Deceleration

Disabled

Enabled or Disabled

Start Deceleration Voltage

60%

0-100 %

Stop Deceleration Voltage

30%

0-59 %

Deceleration Time

5 sec

1-60 sec

Timed Output Time

Off

1-1000 sec, Off

SP2.7

Run Delay Time

1 Sec

1-30 sec, Off

SP2.8

At Speed Delay Time

1 Sec

1-30 sec, Off

SP2.9

SP2.3

SP2.4

SP2.5

SP2.6

Page

2

Starter Configuratio

n

Level

1

No Passowrd Require

d

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Motor Full Load Amps (FLA)

Model dependent

50 - 100% of Unit Max Current Rating
(Model and Service Factor dependent)

SP1.1

Service Factor

1.15

1.00 – 1.3

SP1.2

Overload Class

10

O/L Class 5-30

SP1.3

NEMA Design

B

A-F

SP1.4

Insulation Class

B

A, B, C, E, F, H, K, N, S

SP1.5

Line Voltage

Model dependent

1000 to 7200V

SP1.6

Line Frequency

60

50 or 60 HZ

SP1.7

Page

1

Basic Configuration

Level

1

No Passowrd Require

d