Troubleshooting chart, What to be prechecked first – Toshiba RAS-10SAX User Manual

Page 32

Advertising
background image

– 32 –

9. TROUBLESHOOTING CHART

TROUBLESHOOTING PROCEDURES :

• Following details of “What to be pre-checked first”, make sure of the basic items.

• When there is no trouble corresponding to above, check in detail the faulty parts following “How to judge

faulty parts by symptoms” later.

9-1. What to be Prechecked First

9-1-1. Power Supply Voltage

The line voltage must be AC 220/230/240V. If the line

voltage is not within this range, this air conditioner

may not work normally.

9-1-2. Incorrect Cable Connection between

Indoor and Outdoor Units

The indoor unit is connected to the outdoor unit with 3

cables. Make certain that the indoor and outdoor units

have been connected properly, with terminals assigned

the same numbers wired to each other. If the connec-

tors are not connected as specified, the outdoor unit

will not operate normally.