Toshiba RAS-10SAX User Manual

Page 37

Advertising
background image

– 37 –

Check

code

Check

code

Block

Indoor PC
board

Refrigerant
system

Table 9-2-4

Condition

Indicated when
detected abnormal

Indicated when
detected abnormal

Indicated when
detected abnormal

Indicated when
detected abnormal

Indicated when
detected abnormal

Judgment and action

1. Check thermo sensor.

2. If it is OK, check PC board.

1. Check heat exchanger

sensor.

2. If it is OK, check PC board.

1. Disconnect the power plug

from AC outlet, and pull out
the connector (CN10) for the
motor, then connect the plug
of AC power cord again and
turn the power on.

2. Check the voltage between

pin 1 and 2 of the connector
(CN10).

3. If the output voltage is 35V,

PC board is OK, check
motor.

Replace PC board.

1. Check gas quantity.

(check gas leakage)

2. If it is OK, check heat

exchanger sensor.

3. If heat exchenger sensor is

OK. check overload relay and
thermostat for compressor.

4. If overload relay is OK, check

refrigerant cycle.

5. If refrigerant cycle is OK,

check PC board.

Diagnosis function

Block level

Symptom

Thermo sensor
short/break.

Heat exchanger
sensor short/break.

Indoor fan lock,
abnormality of
indoor fan.

Abnormality of
other indoor unit PC
board.

1) Gas shortage.

(gas leak)

2) Other refrigerant

cycle trouble.

3) Heat exchanger

sensor off/break/
short.

4) Overload relay

Air

Conditioner

status

Continued
operation

Continued
operation

All off

All off

All off

Contents detected by the check codes “ ” to “ ” are stored in memory of the microcomputer even if the power
supply is turned off. Therefore, contents of operations in the past are all displayed.