3-4. only compressor does not operate – Toshiba RAS-10SAX User Manual

Page 40

Advertising
background image

– 40 –

9-3-4. Only Compressor does not Operate

Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.

Does the OPERATION lamp flash?

Does the power turn on by

pushing the [START/STOP] button

of the remote control?

Is cable connection between indoor

and outdoor units correct?

Replace the
PC board.

See "Power can not be turned on".

NO

NO

NO

NO

YES

YES

YES

YES

Is the voltage across the outdoor terminal

( 1 - 2 ) 220/230/240 VAC?

YES

Are all the cords for compressor normal?

Is the compressor motor winding normal?

(Check the winding resistor.)

Is the capacitor for compressor normal?

Is the overload relay normal?

Does the compressor start?

Compressor starts but

it stops after a while?

Cables between indoor and
outdoor units are defective.

Re-wire or replace the defective cords.

Compressor is defective.

Capacitor is defective.

Overload relay is defective.

Compressor is defective.

Correct cabling between indoor
and outdoor units.

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

See "Power can not be turned on".

YES

Is the gas quantity normal?

(Check the pressure)

Gas shortage (Gas leakage)

NO

Compressor is defective

Is the voltage across the indoor terminal

( 1 - 2 ) 220/230/240 VAC?

Relays (RY01, RY02)
or IC31 or IC30 is failure.