9-3. Troubleshooting Flowcharts

9-3-1. Power can not be Turned on (No Operation at All)

<Preliminary checks>

(1) Is the supply voltage normal?

(2) Is the connection to the AC output OK.?

*

Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of

damage of the motor.

PC board

is defective.

Symptom

Operation

Check Items

Main cause

Countermeasure

Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.

Does the OPERATION

lamp flash?

Does the transmission

indicator of remote

control flash normally and

transmit certainly?

Remote control

is defective.

Replace the
remote control.

(No problem)

Does the fuse

(F01) blow?

Replace the main
PC board.

Wrong wiring of

AC cord or connecting

cable is defective.

Replace the
thermal fuse set.
Check connection.

Is the indication voltage

(DC12V or 5V) of main

PC board correct?

Is the voltage

across C02 measured

DC310V~340V?

Refer to the paragraph
"Pre-check", or defective circuit
before power PC board block.

Shut off the power
supply once, and turn
it on again after dis-
connecting the motor
connector CN10

*

.

Is the secondary

voltage of SW

transformer measured

DC35V, DC12V,

and DC7V?

Motor is defective.

Is the secondary

voltage of SW trans-

former (T01) measured

DC35V, DC12V,

and DC7V ?

YES

SW transformer

(T01) or IC (IC01)

for power supply

is defective.

Parts (R21, R109, SG01,

C15, C01, DB01, C02,

IC01, T01) are defective.

Does the power turn

on by pushing the

[START/STOP] button

of the remote control?

NO

YES

YES

NO

NO

YES

YES

NO

NO

NO

YES

YES

NO

YES

YES

NO

Does the thermal

fuse blow?

(Under PF. Terminal)

NO

Replace the main
PC board.