Step 1: set the reference in smart remote mode – Fluke Networks CertiFiber Pro Users Manual User Manual
Page 202

Versiv Cabling Certification Product Family
Technical Reference Handbook
180
Step 1: Set the Reference in Smart Remote Mode
1-1 Turn on the tester and remote and let them sit for a
minimum of 5 minutes. Let them sit longer if they are above
or below ambient temperature.
1-2 Make sure that the home screen shows the correct settings for
the job, and the test type is Smart Remote.
To make sure that other settings are correct, tap the test
setup panel, make sure the correct test is selected on the
CHANGE TEST screen, then tap EDIT to see more settings.
Table 8 on page 172 describes the settings.
1-3 Clean and inspect the connectors on the tester, remote, and
test reference cords.
1-4 On the home screen tap SET REF.
1-5 On the SET REFERENCE screen, tap RUN WIZARD.
Notes
To only set the reference, and not measure the
loss of your test reference cords, tap SKIP WIZARD
on the SET REFERENCE screen.
Fluke Networks recommends that you measure
the loss of your test reference cords each time you
set the reference.
1-6 Make the connections to set the reference, as shown on the
screen and in Figure 81, then tap NEXT to see the completed
connections.
Notes
The SET REFERENCE screen shows reference
connections for the selected reference method.
Figure 81 shows connections for a 1 Jumper
reference.
When you set the reference, align the testers as
shown in Figure 81 to keep the fibers as straight as
possible.