Step 6: do an otdr test from end 1, Connections for launch + tail compensation – Fluke Networks CertiFiber Pro Users Manual User Manual

Page 71

Advertising
background image

Versiv unit with

OptiFiber Pro

module

Adapter

Launch cord

Tail cord

Chapter 2: Get Started

Tutorial: Do a Bi-Directional OTDR Test

49

After you do a test, you can enter the ID for a test you saved
before. This lets you replace results or add different results to a
test you saved before.

GPU27.EPS

Figure 16. Connections for Launch + Tail Compensation

Step 6: Do an OTDR Test from End 1

6-1 Clean all fiber connectors.

6-2 Connect the launch cord to the tester and to the cabling, as

shown in Figure 17.

6-3 Tap TEST or press .