Chapter 3: How to Certify Twisted Pair Cabling

Make Sure Your Tester is Ready to Certify Twisted Pair Cabling

67

Make Sure Your Tester is Ready to Certify

Twisted Pair Cabling

To make sure your tester meets its accuracy specifications, follow
these guidelines:

Keep the tester’s software current. The latest software is
available on the Fluke Networks website. See “Update the
Software” on page 360.

Set the reference for the twisted pair adapters every 30 days.
See “Set the Reference” on page 70.

Make sure you select the correct cable type for the job, and
that the NVP for the cable is correct. See Table 2 on page 72.

Make sure you select the correct test limit for the job. See
Table 2 on page 72.

Make sure the cords and connectors for all test equipment
and patch cords are in good condition.

Make sure the battery is fully charged.

Send the modules to a Fluke Networks service center every 12
months for factory calibration.

About Link Interface Adapters

Link interface adapters let you connect the DSX CableAnalyzer to
different types of twisted pair links. Figure 23 shows how to
attach and remove adapters.

Caution

To prevent damage to the cables on the permanent
link adapters and to make sure your test results are
as accurate as possible, do not twist, pull on, pinch,
crush, or make kinks in the cables. See Figure 24 on
page 69.