Laurel Electronics LAUREATE SERIES DPM User Manual

Page 25

Advertising
background image

To set up the range using coordinates of 2 points, values for low signal input, low display, high
signal input and high display are entered. The following example uses this scaling method.
Signal input is 4 to 20mA and displayed value is 000.00 (at 4mA) to 100.00 (at 20mA). When
setting up the meter, it may be necessary to enable some menu items. See Section 9 for further
information.

-23-

Press

to select 2.0a,

20.0a, 200.0a (milliamps) or
5.0A (Amps).
(.20U, 2.0U, 20.0U, 200.0U
or 660.0U if voltage input)

Press

until dC A (DC

Amperes) is displayed.
(dC U if voltage input).

Press the

key to display

InPut (Input type selection).
Note: Selection of input type
& range must match jumper
selection in Section 12.1.

Press

to display status

and select left digit. Press

again to select another

digit. Selected digit will flash.

Press

to select value for

flashing digit.
Digit 1:

"0"= 20,000 cts
"3"=2,000 cts

Digit 4:

"0"=scale & offset
"1"=2- coordinate

1 2 3 4 5

1 2 3 4 5

Press the

key to display

dEcPt (Decimal point).

Press

to display decimal

point location

Press to change decimal
point location.

Press

to display value

and select left digit. Press
again to select another digit..
Dec pt. fixed by input range

Press the

key to display

Lo in (Low signal input value).

Use to set digit values and
set to 04.000 (4 mA). Most
significant digit may be set to
0 thru 9 and -0 thru -9.

Use

to set digit values

and set to 000.00 .

Press the

key to display

Lo rd (Desired meter reading
at low signal input).

Press the

key to display

Hi in (High signal input value).

Press

to display value

and select left digit. Press
again to select another digit.
Decimal point set by Dec.Pt.

DIGIT SELECT KEY

VALUE SELECT KEY

Press

to display value

and select left digit. Press
again to select another digit.
Dec pt. fixed by input range

Use to set digit values and
set to 20.000 (20 mA).

Press the

key to display

SEtuP. (Basic setup)
See Section 9, Page 10 for
detailed description of selec-
tions for digits 1 through 5.

MENU KEY