Chapter 2 Installation

Electrical Installation

Multi-Mon

Multiple Circuit Energy Monitor

15

Safety Req

Safety Req

Safety Req

Safety Requirements

uirements

uirements

uirements

To ensure safety requirements the Multi-Mon must be grounded - the
protective ground terminal should be connected to protective earth with a
copper conductor or strap with minimal length (less than 1 m desirable) and
cross-section 5.3 mm

2

(AWG10) at least.

The properly marked external 3-pole disconnect device with circuit-breaker
and a fuse 6A, 600V in every pole should be installed between voltage
measurement terminals and power lines, located as close as possible (less
than 2 m recommended) to the Multi-Mon, as shown in figure 2-5 .

Figure 2

Figure 2

Figure 2

Figure 2----7 External

7 External

7 External

7 External CT

CT

CT

CT connection to

connection to

connection to

connection to meter CT

meter CT

meter CT

meter CT