Real time clock setting, Transformer correction – E-Mon E-MM-RTU-D-N User Manual

Page 31

Advertising
background image

Chapter 3 Multi-Mon Display Operations

Menu Operations

Multi-Mon

Multiple Circuit Energy Monitor

31

Real Time Clock Setting

Real Time Clock Setting

Real Time Clock Setting

Real Time Clock Setting

This menu allows you to adjust internal real time clock.

To enter the menu, select the RTC entry from the main menu, and then
press the ENTER button.

To adjust the clock:

1. Highlight a time or date item you want to change item by briefly pressing

the SELECT button.

2. Adjust the selected item with the UP/DOWN buttons.

3. Highlight the next item you want to change and adjust it in the same

manner.

4. To store your new date and time, press the ENTER button. If you

confirm the time change while the seconds item is highlighted, the
seconds’ reading will be zeroed, otherwise seconds stay unchanged.

To exit the menu, highlight the menu name (upper-left item) with the
SELECT button, and then press the ENTER button.

Basic Device Settings

Basic Device Settings

Basic Device Settings

Basic Device Settings

This menu allows you to define the general characteristics of the electrical
network.

To enter the menu, select the Basic entry from the main menu, and then
press the ENTER button. For instructions on navigating in the menu, see

Viewing and Changing Setup Items

.

The following table lists available options.

Label

Label

Label

Label

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

Pt

Pt

Pt

Pt

PT Ratio

1.0-6500.0

1.0

The phase potential
transformer’s primary to
secondary ratio

Frequency

Frequency

Frequency

Frequency

Nominal
frequency

50, 60 Hz

60 Hz

The nominal power
frequency

PowDmdPer

PowDmdPer

PowDmdPer

PowDmdPer

Block power
demand period

1, 2, 5, 10,
15, 20, 30,
60 min

30

The length of the demand
period for power demand
calculations

Num.Per.

Num.Per.

Num.Per.

Num.Per.

The number of
blocks in the
sliding window

1-15

1

The number of blocks to
be averaged for sliding
window demands

VDmnPer.

VDmnPer.

VDmnPer.

VDmnPer.

Volt demand
period

0-9000 sec

900

The length of the demand
period for volt demand
calculations

ADmdPer.

ADmdPer.

ADmdPer.

ADmdPer.

Ampere
demand period

0-9000 sec

900

The length of the demand
period for ampere
demand calculations

Transformer Correction

Transformer Correction

Transformer Correction

Transformer Correction

Transformer correction allows you to compensate ratio and phase angle
inaccuracies of the user voltage and current instrument transformers. To
enter the menu, select the T.Corr. entry from the main menu, and then press
the ENTER button. For instructions on navigating in the menu, see

Viewing

and Changing Setup Items

.

The following table lists available options.

RTC Jun 06,2005

Time 20:47:06

SELECT

RTC Jun 06,2005

Time 20:47:06

RTC Jun 06,2006

Time 20:47:06

ENTER

RTC Jun 06,2006

Time 20:47:06

Basic Exit

Basic Frequency

60

ENTER