Appendix A Technical Specifications

Multi-Mon

Multiple Circuit Energy Monitor

61

Appendix A

Appendix A

Appendix A

Appendix A

Technical Specifications

Technical Specifications

Technical Specifications

Technical Specifications

Environmental Co

Environmental Co

Environmental Co

Environmental Conditions

nditions

nditions

nditions

Indoor use only

BFM is intended for operation in environment where normally only non-
conductive pollution occurs as defined for pollution degree 2 (UL61010,
3.6.6.2)

Operating Temperature: -40°C to 70°C (-40°F to 158°F)

Storage Temperature: -40°C to 80°C (-40°F to 176°F)

Humidity: 0 to 95% non-condensing

Altitude: 2,000m max

Input Ratings

Input Ratings

Input Ratings

Input Ratings

Parameter

Parameter

Parameter

Parameter

Value

Value

Value

Value

Fundamental frequency

50/60 Hz

AC Voltage

AC Voltage

AC Voltage

AC Voltage

4 wires, 3 phases+ neutral

Reference Voltage

(115) 88-136 VAC or
(230/400 – 277/480) 176-320 VAC

Maximum Line to Neutral voltage

320 V

Maximum Line to Line voltage

544V

Burden per phase

<1.5W

AC Voltage for Measurement and
Power supply

Maximal apparent power consumed
from power line < 10VA

Isolation

2.5 kV RMS, 60Hz, 1 min
Leakage current < 0.005A per circuit
Impulse 1.2/50µS 6 kV

Fuse rating

6A, 600V

AC Current

AC Current

AC Current

AC Current

36 current circuits

Maximum measurable current Imax
(In=50A)

400 A

Test current

15 A

Maximum overcurrent for 0.5 cycle of
fundamental frequency

3000 A

Burden per phase

< 1 VA

Isolation

4 kV RMS, 60Hz, 1 min

LCD Display

LCD Display

LCD Display

LCD Display

No. Of Digits

2 Rows, 16 digits in each

Operating Temperature:

-20°C to 70°C (-4°F to 158°F)

Non-volatile Memory storage life

20 years

RTC storage upon loss of power

24 Hours minimum

1 Week typical

Push buttons

4

Voltage inputs terminal

10 AWG Max.

Communication Ports

Communication Ports

Communication Ports

Communication Ports

COM2 (Optional modules)

COM2 (Optional modules)

COM2 (Optional modules)

COM2 (Optional modules)

Serial EIA RS

Serial EIA RS

Serial EIA RS

Serial EIA RS----232 optically isolated port

232 optically isolated port

232 optically isolated port

232 optically isolated port

Connector Type: DB9 female.

Baud Rate: up to 115.2 kbps.

Supported Protocols: Modbus RTU/ASCII.

RS

RS

RS

RS----422/RS

422/RS

422/RS

422/RS----485 optically isolated port

485 optically isolated port

485 optically isolated port

485 optically isolated port

Connector Type: removable, captured-wire, 5 terminals.

Wire Size: up to 12 AWG (up to 2.5 mm

2

).

Baud Rate: up to 115.2 kbps.