Measurement specifications – E-Mon E-MM-RTU-D-N User Manual

Page 63

Advertising
background image

Appendix A Technical Specifications

Multi-Mon

Multiple Circuit Energy Monitor

63

Measurement Specifications

Accuracy

Accuracy

Accuracy

Accuracy

Parameter

Parameter

Parameter

Parameter

Full Scale @ Input

Full Scale @ Input

Full Scale @ Input

Full Scale @ Input

Range

Range

Range

Range

% Reading

% Reading

% Reading

% Reading

% FS

% FS

% FS

% FS

Conditions

Conditions

Conditions

Conditions

Range

Range

Range

Range

Voltage

V

L

= 230V

0.3

0.05

184 to 260 V

0 to Vmax= 600 V

Line current

Instrument current
transformer CTs
I

L

= 100A

0.5

0.05

1 to 100% FS

0 to CT primary current
Starting current: 0.1%
FS

Active power

2 × Vmax × I

L

/1000,

kW

1

0.02

|PF| ≥ 0.5 1

-120.000 to 120.000
kW

Reactive power

2 × Vmax × I

L

/1000,

kvar

1

0.02

|PF| ≤ 0.9 1

-120.000 to 120.000
kvar

Apparent power

2 × Vmax × I

L

/1000,

kVA

1

0.02

|PF| ≥ 0.5 1

0 to 120.000 kVA

Power factor

1.0

-

1.0

|PF| ≥ 0.5, I ≥ 2% FSI

-0.999 to +1.000

Frequency

0.02

-

50 Hz

50 Hz

50 Hz

50 Hz: 39.00 to 65.00 Hz
60 Hz

60 Hz

60 Hz

60 Hz: 45.00 to 70.00 Hz

39 Hz up to 70 Hz

Active energy import

4

Class 1.0 under conditions as per IEC 62053-21:2003

0 to 99,999,999.9 kWh

Reactive energy
import/export

Class 1.0 under conditions as per IEC 62053-21:2003,
|PF| ≤ 0.9

0 to 99,999,999.9 kvarh

Apparent energy

Class 1.0 under conditions as per IEC 62053-21:2003

0 to 99,999,999.9 kVAh

1

@ 80% to 115% of voltage FS and 1% to 100% of current FS

FSV - voltage full scale

FSI - current full scale

Notes

Notes

Notes

Notes
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include
inaccuracies introduced by the user's potential and current transformers. Accuracy calculated at 1-second average.

2. Specifications assume: voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF; reference operating
temperature: 20°C - 26°C.

3. Measurement error is typically less than the maximum error indicated here.

4. Accuracy of the device without CT complies to IEC 62053-22 class 0.5S standard


Advertising
This manual is related to the following products: