Chapter – E-Mon E-MM-RTU-D-N User Manual

Page 7

Advertising
background image

Chapter 1 General Information

Multi-Mon

Multiple Circuit Energy Monitor

7

Chapter

Chapter

Chapter

Chapter 1

1

1

1 General Information

General Information

General Information

General Information

The Multi-Mon is a 3-phase, multi-channel, multi-function energy meter
suitable for use in single-phase and multi-phase electrical networks.

Meter highlights

Meter highlights

Meter highlights

Meter highlights

•

Multi-channel submetering – up to 36 single-phase or 18 two-phase
or 12 three-phase submeters in a single device. Any combination of
single-, two-, and three-phase consumers can be chosen up to a
total of 36 current inputs.

•

Automatic totalization energy from different sub-consumers

Fea

Fea

Fea

Features

tures

tures

tures

•

Calibrated to meet Class 0.5S active energy and Class 1 reactive
energy meter accuracy

•

3-phase/2-phase/single-phase meters (true RMS, volts, amps,
power, power factor, neutral current)

•

Ampere/Volt demand meter

•

Time-of-Use, 4 energy/demand registers x 6 tariffs

1

, 4 seasons x 4

types of days, 8 tariff changes per day, easy programmable tariff
schedule

•

Import/export energy and power demands

•

Automatic 120–day daily profile for import/export

2

energy and

maximum demand readings (total and tariff registers) separate for
each submeter

•

Event recorder for logging internal diagnostic events and setpoint
operations

•

Data recorders; programmable periodical data logs separate for
each submeter

•

Embedded programmable controller (4 control setpoints,
programmable thresholds and delays) separate for each submeter

•

Easy to read 2-row x 16 characters LCD display with backlight
(Multi-Mon only)

•

50/60 Hz operation

•

Internal clock, keeping the clock running over one week without
external power

•

Highly Accurate Current Transformer with overvoltage protection
diodes to avoid any damage while disconnecting the primary
current sensor

•

Standard RS-485 serial port

•

Optional second communication port. Communication options
available:

RS-232
RS-422/485
56K Dial-up modem
Ethernet 10/100BaseT

•

Modbus RTU and Modbus ASCII communication protocols

•

Easy field upgrading device firmware through any communication
port

1

From Firmware version 18.4.1

2

From Firmware version 18.5.1

Advertising