Chapter 4 Power Software Configuration tool

General Meter Setup

Multi-Mon

Multiple Circuit Energy Monitor

43

General Meter Setup

General Meter Setup

General Meter Setup

General Meter Setup

This section describes how to configure the Multi-Mon for your particular
environment and application using Power Software.

Basic Meter Setup

Basic Meter Setup

Basic Meter Setup

Basic Meter Setup

Before operating your meter, provide the device with basic information about
your electrical network.

To enter the setup dialog, select the device site from the list box on the
Power Software toolbar, and then select General Setup from the Meter Setup
menu.

The following table lists available device configuration options.

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

Basic Configuration

Basic Configuration

Basic Configuration

Basic Configuration

PT Ratio

1.0-6500.0

1.0

The phase potential transformer’s
primary to secondary ratio

Primary current

1-10000 A

50A

The CT primary current of the
submeter’s; for information only.

Nominal frequency

50, 60 Hz

60Hz

The nominal power frequency

Demand Setup

Demand Setup

Demand Setup

Demand Setup

Block power
demand period

1, 2, 5, 10, 15, 20,
30, 60 min

30

The length of the demand period for
power demand calculations

The number of
blocks in the sliding
window

1-15

1

The number of block demand periods
to be averaged for sliding window
demands

Volt demand period 0-9000 sec

900 sec

The length of the demand period for
volt demand calculations

Ampere demand
period

0-9000 sec

900 sec

The length of the demand period for
ampere demand calculations

Device Options

Device Options

Device Options

Device Options

Power calculation
mode

S=f(P, Q) (using
reactive power),
Q=f(S, P) (using
non-active power)

S=f(P, Q)

The method used for calculating
reactive and apparent powers (see
“Power Calculation Modes” below)