Chapter 3 Multi-Mon Display Operations

Menu Operations

32

Multi-Mon

Multiple Circuit Energy Monitor

Label

Label

Label

Label

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

Ratio V1

Ratio V1

Ratio V1

Ratio V1----V3

V3

V3

V3

V1-V3 voltage
transformer
ratio correction
factor

0.700 to 1.300

1.000

The ratio of the true
transformer ratio to the
marked ratio.

Angle V1

Angle V1

Angle V1

Angle V1----V3

V3

V3

V3

V1-V3
transformer
phase angle
error, minutes

-600 to 600

0

The phase
displacement, in
minutes, between the
primary and secondary
values. The phase
angle of a voltage
transformer is positive
when the secondary
value leads the primary
value.

Ratio I1

Ratio I1

Ratio I1

Ratio I1----IIII36

36

36

36

I1-I36 current
transformer
ratio correction
factor

0.700 to 1.300

1.000

The ratio of the true
transformer ratio to the
marked ratio.

Angle I1

Angle I1

Angle I1

Angle I1----I36

I36

I36

I36

I1-I36
transformer
phase angle
error, minutes

-600 to 600

0

The phase
displacement, in
minutes, between the
primary and secondary
values. The phase
angle of a current
transformer is positive
when the secondary
value leads the primary
value.

Device Options

Device Options

Device Options

Device Options

This menu allows you to select some user-configurable device options or put
the Multi-Mon into energy test mode.

To enter the menu, select the Options entry from the main menu, then press
ENTER. For instructions on navigating in the menu, see

Viewing and

Changing Setup Items

.

The following table lists available options.

Label

Label

Label

Label

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

PowMode

PowMode

PowMode

PowMode

Power
calculation
mode

Reactive,
NonActive (non-
active power)

Reactive

The method used for
calculating reactive
and apparent powers

ErgyRoll

ErgyRoll

ErgyRoll

ErgyRoll

Energy roll
value

100000.0-
100000000.0
kWh

100000000.0

The value at which
energy counters roll
over to zero

TestMode

TestMode

TestMode

TestMode

Energy test
mode

OFF, Wh, varh OFF

Setting this option
puts the device into
the energy test mode

PlsConst

PlsConst

PlsConst

PlsConst

Wh LED pulse
rate,
Wh/pulse

0.01-100.00

5.40Wh/pulse
(one
equivalent
disk
revolution)

LED pulse constant -
the amount of
accumulated energy
giving one pulse via
“Wh” LED

WhLEDSrc

WhLEDSrc

WhLEDSrc

WhLEDSrc Energy LED

source

1-40, None

1

Selects a submeter as
a LED pulsing source

Communication Ports

Communication Ports

Communication Ports

Communication Ports

These two menus allow you to configure parameters for communication
ports COM1 and COM2. The Multi-Mon automatically detects a replaceable
communication module and will not allow you to change the baud rate and
data format for the Dial-up modem, and for the Ethernet and RF modules.

Options

Exit

Options PowMode
Reactive

ENTER