Channel assignments – E-Mon E-MM-RTU-D-N User Manual

Page 44

Advertising
background image

Chapter 4 Power Software Configuration tool

General Meter Setup

44

Multi-Mon

Multiple Circuit Energy Monitor

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

Energy roll value,
kWh

100000.0 kWh
1000000.0 kWh
10000000.0 kWh
100000000.0 kWh

100000000.0

The value at which energy counters
roll over to zero

Energy LED pulse
rate, Wh/pulse

0.01-100.00

5.40 Wh/pulse
(one equivalent
disk revolution)

LED pulse constant - the amount of
accumulated energy (in secondary
readings) giving one pulse via “Wh”.

Energy LED Test

Disabled,
Wh Pulses,
varh Pulses

Disabled

The type of accumulated energy
giving pulses via “Wh” LED.

Energy LED Pulse
source

SubMeter 1,
SubMeter 2,

SubMeter 40

SubMeter 1

The submeter uses as source of
accumulated energy giving pulses via
“Wh” LED.

Volts Scale, V

60-600 V

600 V

The maximum voltage scale allowed,
in secondary volts. See

Data Scales

in

Appendix E

Power Calculation Modes

Power Calculation Modes

Power Calculation Modes

Power Calculation Modes

The power calculation mode option allows you to change the method for
calculating reactive and apparent powers in presence of high harmonics. The
options work as follows:

1. When the reactive power calculation mode is selected, active and reactive
powers are measured directly and apparent power is calculated as:

2

2

Q

P

S

+

=

This mode is recommended for electrical networks with low harmonic
distortion, commonly with THD < 5% for volts, and THD < 10% for currents.
In networks with high harmonics, the following method is preferable.

2. When the non-active power calculation mode is selected, active power is
measured directly, apparent power is taken as product S = V x I, where V
and I are the RMS volts and amps, and reactive power (called non-active
power) is calculated as:

2

2

P

S

N

=

Channel Assignments

Channel Assignments

Channel Assignments

Channel Assignments

The Channel Assignments setup allows you to link the device current
terminals to submeters so they can monitor them. Additionally, this setup
allows you to specify the primary current rating of the current transformers
connected to the device terminals. The number of the selected current inputs
for a submeter specifies if it will be a single-, two-, or three-phase meter.

Always selec

Always selec

Always selec

Always select your submeters (both metering and totalization) in a sequence

t your submeters (both metering and totalization) in a sequence

t your submeters (both metering and totalization) in a sequence

t your submeters (both metering and totalization) in a sequence

without gaps so that your device does not occupy unnecessary network

without gaps so that your device does not occupy unnecessary network

without gaps so that your device does not occupy unnecessary network

without gaps so that your device does not occupy unnecessary network
addresses.

addresses.

addresses.

addresses.

To enter the setup dialog, select the device site from the list box on the
Power Software toolbar, select General Setup from the Meter Setup menu,
and then click on the Channel Assignments tab.