Local network settings, Local settings – E-Mon E-MM-RTU-D-N User Manual

Page 33

Advertising
background image

Chapter 3 Multi-Mon Display Operations

Menu Operations

Multi-Mon

Multiple Circuit Energy Monitor

33

To enter the menu, select the COM1 or COM2 entry from the main menu,
and then press the ENTER button. For instructions on navigating in the
menu, see

Viewing and Changing Setup Items

.

The following table lists available port options.

Label

Label

Label

Label

Parameter

Parameter

Parameter

Parameter

Options

Options

Options

Options

Default

Default

Default

Default

Description

Description

Description

Description

Protocol

Protocol

Protocol

Protocol

Communication
s protocol

Modbus RTU,
Modbus ASCII

Modbus
RTU

The communications
protocol for the port

Interface

Interface

Interface

Interface

Port interface

RS485
RS485, RS232,
Modem,
Ethernet, RF

COM1
COM2

Not changeable;
automatically detected
by the device

Address

Address

Address

Address

Device address 1-247

1

Device’s base network
address (see

Submeter

Addressing

)

Baud rate

Baud rate

Baud rate

Baud rate

Baud rate

2.4-115.2 kbps

19.2 kbps

The port baud rate

Data/Prty

Data/Prty

Data/Prty

Data/Prty

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU protocol

Send Delay

Send Delay

Send Delay

Send Delay Transmission

delay

0-1000 ms

5 ms

The minimum time after
the last request
character is received to
start the transmission.

Chr.Tmout

Chr.Tmout

Chr.Tmout

Chr.Tmout

Inter-character
timeout

0-1000 ms

4 ms

The maximum time the
line is allowed to idle
before closing a
connection in the
Modbus RTU protocol

NOTE

NOTE

NOTE

NOTE

When using the ExpertPower

When using the ExpertPower

When using the ExpertPower

When using the ExpertPower

client (see

client (see

client (see

client (see

Configuring eXpertPower Client

Configuring eXpertPower Client

Configuring eXpertPower Client

Configuring eXpertPower Client

),

),

),

),

submeter address

submeter address

submeter address

submeter address 99 on the Ethernet port COM2 is reserved for the

99 on the Ethernet port COM2 is reserved for the

99 on the Ethernet port COM2 is reserved for the

99 on the Ethernet port COM2 is reserved for the Multi

Multi

Multi

Multi----

Mon

Mon

Mon

Mon router and must not fall inside the range of the submeter addresses for

router and must not fall inside the range of the submeter addresses for

router and must not fall inside the range of the submeter addresses for

router and must not fall inside the range of the submeter addresses for

this port.

this port.

this port.

this port.

Local Network Settings

Local Network Settings

Local Network Settings

Local Network Settings

This menu allows you to configure the Ethernet modem (if present) for direct
communications through the LAN or the Internet.

To enter the menu, select the Net entry from the main menu, and then press
the ENTER button. For instructions on navigating in the menu, see

Viewing

and Changing Setup Items

.

The following table lists available Ethernet options.

Label

Label

Label

Label

Default

Default

Default

Default

Description

Description

Description

Description

IP Address

IP Address

IP Address

IP Address

192.168.0.203

Device IP address

Subnet Mask

Subnet Mask

Subnet Mask

Subnet Mask

255.255.255.0

Subnet mask

Def.Gateway

Def.Gateway

Def.Gateway

Def.Gateway

192.168.0.1

Default gateway


Local Settings

Local Settings

Local Settings

Local Settings

This menu allows you to configure your local time zone settings.

To enter the menu, select the Local entry from the main menu, and then
press the ENTER button. For instructions on navigating in the menu, see

Viewing and Changing Setup Items

.

The following table lists available options.

COM1

Exit

COM1

Protocol

Modbus RTU

ENTER

Net Exit

Net IP Address

192.168.000.203

ENTER

Local Exit

Local Country
Default

ENTER