Grounding the scale – Fairbanks Tundra Series Truck Scale User Manual
Page 43
Section 5: Electrical Installation
12/12
43
51193 Revision 5
5.7. GROUNDING THE SCALE
Intalogix
™
Technology systems requires two (2) ground rods in the pit for proper
connection.
•
Pit power supply connects to one ground rod, and the weighbridge
connects the other one.
•
For accurate operation and protection against damage from lightning strikes,
all of the components of the system must be properly grounded.
Use the following guidelines to correctly ground the system:
•
Use 8 AWG or larger wire, or braided ground straps.
•
All ground connections should be two feet (2’) or less, or as conditions warrant
as short as possible.
•
The SSCs and PPSs enclosures attach connections to the weighbridge. The
weighbridge is then connected to a pit ground rod.
•
The insulated WHITE WIRE from the PPS connects directly to the separate
ground rod,
and not to the same rod as the weighbridge.