Indicator and accessories. test and calibration, Proper grounding is required, Grounding the scale, continued – Fairbanks Tundra Series Truck Scale User Manual
Page 44
Advertising
Section 5: Electrical Installation
12/12
44
51193 Revision 5
5.7. GROUNDING THE SCALE, CONTINUED
•
The 117 VAC SVP Unit connects to a ground at the instrument’s incoming
power outlet.
─ Use a voltmeter to test the electrical power source available.
─ The Neutral-to-Ground voltage level must be 0.2 VAC or less.
5.8. INDICATOR AND ACCESSORIES. TEST AND CALIBRATION
Use the correct indicator manual(s) to calibrate and test the scale. Also use the
correct accessory manual(s) for proper setup and testing of their functionality and
operation.
C A U T I O N
Proper grounding is
REQUIRED
so the Surge Voltage Protection (SVP) adequately protects the scale!