POWER WIRING

WIRING

POWER WIRING

This operator can be wired for either 120 Vac or 240 Vac or a solar

panel (not provided). Follow the directions according to your application.

For dual gate applications, power will have to be connected to each

operator. Main power supply and control wiring MUST be run in

separate conduits.
NOTE:
If using an external receiver use shielded wire for the connections and

mount the receiver away from the operator to avoid interference with the operator.

240 VAC ONLY

If using the 240 Vac option a heater cannot be used. The accessory outlet is disabled

and cannot be used with the 240 Vac option.

1

Remove the outlet housing from the electrical box by removing the

screws (2).

2

Pull the outlet housing out and locate the power wiring connector on the

EMI board.

3

Unplug the power wiring connector from the 120 Vac socket (factory default

location) and plug it into the 240 Vac socket.

4

Replace the outlet housing by securing with the screws. The operator is now set

for 240 Vac operation.

Outlet Housing

Power Wiring Connector

(120 Vac Socket, factory default)

240 Vac Socket

AMERICAN WIRE

GAUGE (AWG)

MAXIMUM WIRE

LENGTH (120 VAC)

MAXIMUM WIRE

LENGTH (240 VAC)

14

130 feet

260 feet

12

205 feet

410 feet

10

325 feet

650 feet

8

520 feet

1040 feet

6

825 feet

1650 feet

4

1312 feet

2624 feet

EMI Board

NOTE: Use copper conductors ONLY.

120 VAC AND 240 VAC

Junction Box Cover

1

Turn off the AC power from the main power source circuit breaker.

2

Run the AC power wires to the operator.

3

Remove the junction box cover.

4

Connect the green wire to the earth ground rod and AC ground using a wire

nut. NOTE: The earth ground rod can be grounded to the chassis.

5

Connect the white wire to NEUTRAL using a wire nut.

6

Connect the black wire to HOT using a wire nut.

7

Replace the junction box cover. Ensure the wires are not pinched.