A B N 1 2 , S D N 1 2 , S D N 1 2 P L , N 4 1 2 C D ,
N 4 1 2 C S T D , N 4 1 2 C S S S T D , S N 4 & S S N 4 X S E R I E S E N C L O S U R E S
D I S C O N N E C T S PA C E O C C U P I E D & AVA I L A B L E W I R I N G S PA C E I N F O R M AT I O N

F20

www.hubbell-wiegmann.com

Data Subject To Change Without Notice

FRAME

MAXIMUM

CIRCUIT BREAKER

CIRCUIT BREAKER

SIZE

AMP RATING

HEIGHT X

WIDTH Y

E150

1 5 0 A

6 . 3 1

4 . 1 2

SE150

1 5 0 A

6 . 3 1

4 . 1 2

SF250

2 5 0 A

1 0 . 1 2

4 . 1 2

SG600

6 0 0 A

1 0 . 0 9

5 . 5 0

SK1200

1 2 0 0 A

1 5 . 5 0

8 . 2 5

G E N E R A L E L E C T R I C C I R C U I T B R E A K E R S W I T H S P E C T R A F L E X

C A B L E O P E R AT O R S

F o r e n c l o s u r e s t h a t

a c c e p t t h e s e d e v i c e s ,

s e e p a g e s F 2 - F 9 .

F o r e n c l o s u r e s t h a t

a c c e p t t h e s e d e v i c e s ,

s e e p a g e s F 1 0 - F 1 3 .

FRAME

BREAKER

FLANGE-MOUNTING

OPERATING

SIZE

MECHANISM

HANDLE**

CABLE*

E150

S C O M 1 A

S C H 1

S C 3 L

SE150/SF250

S C O M 1 E F

S C H 1

S C 3 L

SG600

S C O M 1 G

S C H 1

S C 3 L

SK1200

S C O M 1 K

S C H 2 K

S C 3 H

* Operating cables are available in 3-foot to 10-foot lengths. (The number 3 in the catalog number denotes

3-foot cable.)

** Add “X” for NEMA 4 or 4X flange-mounted handle.

Space Occupied by Circuit Breaker

• The General Electric Spectra-Flex

system allows the circuit breaker to be positioned independent from

the flange-mounted handle mechanism.

• Refer to National Electrical Code

®

article 430-10(b) for wiring space "WB" required for line side conductors.

• Choose the operating cable length based on placement of the circuit breaker in the enclosure ensuring a 3"

minimum bending radius for the cable.

• Space occupied by circuit breaker is determined by overall circuit breaker size ("X" height and "Y" width)

plus "WB" wire bend space and location "G" as selected from right to left.

SWITCH

AMP

FUSE

FUSE

DISCONNECT

DISCONNECT

RATING

CLIP

CLASS

HEIGHT X

WIDTH Y

MCS603R

3 0 A

N o f u s e

5 . 5 2

6 . 1 3

MCS603R

3 0 A

3 0 A - 2 5 0 V

H , K , R

8 . 1 1

6 . 1 3

MCS603R

3 0 A

3 0 A - 6 0 0 V

H , K , R

1 0 . 1 1

6 . 1 3

MCS603R

3 0 A

3 0 A - 6 0 0 V

J

8 . 4 8

6 . 1 3

MCS606R

6 0 A

N o f u s e

5 . 5 2

6 . 1 3

MCS606R

6 0 A

6 0 A - 2 5 0 V

H , K , R

7 . 8 6

6 . 1 3

MCS606R

6 0 A

6 0 A - 6 0 0 V

H , K , R

1 0 . 3 8

6 . 1 3

MCS606R

6 0 A

6 0 A - 6 0 0 V

J

8 . 3 6

6 . 1 3

MCS610R

1 0 0 A

N o f u s e

7 . 5 9

7 . 3 8

MCS610R

1 0 0 A

1 0 0 A - 2 5 0 V

H , K , R

1 1 . 8 5

7 . 3 8

MCS610R

1 0 0 A

1 0 0 A - 6 0 0 V

H , K , R

1 3 . 8 5

7 . 3 8

MCS610R

1 0 0 A

1 0 0 A - 6 0 0 V

J

1 0 . 6 0

7 . 3 8

MCS620R

2 0 0 A

N o f u s e

9 . 0 2

9 . 1 7

MCS620R

2 0 0 A

2 0 0 A - 2 5 0 V

H , K , R

1 4 . 7 0

9 . 1 7

MCS620R

2 0 0 A

2 0 0 A - 6 0 0 V

H , K , R

1 7 . 2 0

9 . 1 7

MCS620R

2 0 0 A

2 0 0 A - 6 0 0 V

J

1 3 . 3 2

9 . 1 7

I - T- E D I S C O N N E C T S W I T C H E S F O R M A X - F L E X

O P E R AT O R S

F o r e n c l o s u r e s t h a t

a c c e p t t h e s e d e v i c e s ,

s e e p a g e s F 2 - F 9 .

F o r e n c l o s u r e s

t h a t a c c e p t t h e s e

d e v i c e s , s e e

p a g e s F 1 0 - F 1 3 .

ABN12, SDN12, SDN12PL, N412CD,

SN4 & SSN4X

N412CSTD, N412CSSSTD, SN4 & SSN4X

WALL-MOUNTS

ABN12, SDN12, SDN12PL, N412CD,

SN4 & SSN4X

N412CSTD, N412CSSSTD, SN4 & SSN4X

WALL-MOUNTS

Advertising