Yokogawa EJX115A User Manual
Page 11
 
<2. Handling Cautions>
9
IM 01C25A01-01E
Note 2. Entity Parameters
•	 Intrinsically	safe	ratings	are	as	follows:
	 Maximum	Input	Voltage	(Vmax/Ui)	=	30	V
	 Maximum	Input	Current	(Imax/Ii)	=	200	mA
	 Maximum	Input	Power	(Pmax/Pi)	=	0.9	W
	 Maximum	Internal	Capacitance	(Ci)	=	10	nF
	 Maximum	Internal	Inductance	(Li)	=	0	µH
•	 Type	"n"	or	Nonincendive	ratings	are	as	follows:
	 Maximum	Input	Voltage	(Vmax/Ui)	=	30	V
	 Maximum	Internal	Capacitance	(Ci)	=	10	nF
	 Maximum	Internal	Inductance	(Li)	=	0	µH
•	 Installation	Requirements
	 Uo	≤	Ui,		Io	≤	Ii,	Po	≤	Pi,	
	 Co	≥	Ci	+	Ccable,	Lo	≥	Li	+	Lcable
	 Voc	≤	Vmax,	Isc	≤	Imax,	
	 Ca	≥	Ci	+	Ccable,	La	≥	Li	+	Lcable
	 Uo,	Io,	Po,	Co,	Lo,	Voc,	Isc,	Ca	and	La	are	
parameters of barrier.
Note 3. Installation
• In any safety barreir used output current must
be	limited	by	a	resistor	'R'	such	that	Io=Uo/R	or	
Isc=Voc/R.
•	 The	safety	barrier	must	be	CSA	certified.
•	 Input	voltage	of	the	safety	barrier	must	be	less	
than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian
Electrical Code Part I and Local Electrical Code.
• Dust-tight conduit seal must be used when
installed in Class II and III environments.
• The instrument modification or parts replacement
by	other	than	authorized	representative	of	
Yokogawa	Electric	Corporation	and	Yokogawa	
Corporation	of	America	is	prohibited	and	will	
void	Canadian	Standards	Intrinsically	safe	and	
nonincendive	Certification.
F0206.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters
Safety Barrier
Supply
Hazardous Location
Nonhazardous Location
General
Purpose
Equipment
+ 
– 
+ 
– 
+ 
– 
+ 
– 
[Intrinsically Safe]
Group IIC, Zone 0
F0207.ai
Pressure Transmitters
Supply
Hazardous Location
Nonhazardous Location
+ 
– 
+ 
– 
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
CSA Certified
Equipment
([nL] or
nonincendive)
Group IIC, Zone 2
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJX/EJA-E Series pressure transmitters
with	optional	code	/CF1	are	applicable	for	use	in	
hazardous	locations:
•	 Certificate:	2014354
•	 Applicable	Standard:		C22.2	No.0,	
C22.2	No.0.4,		C22.2	No.0.5,		C22.2	No.25,		
C22.2	No.30,		C22.2	No.94,	C22.2	No.61010-1,	
C22.2	No.60079-0,	C22.2	No.60079-1
•	 Explosion-proof	for	Class	I,	Groups	B,	C	and	D.
•	 Dustignition-proof	for	Class	II/III,	Groups	E,	F	and	
G.
•	 Enclosure:	TYPE	4X
•	 Temperature	Code:	T6...T4
•	 Ex	d	IIC	T6...T4			
•	 Enclosure:	IP66/IP67
•	 Maximum	Process	Temperature:	120°C	(T4),	
100°C (T5), 85°C (T6)
• Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specified.
•	 Supply	Voltage:	42	V	dc	max.
•	 Output	Signal:	4	to	20	mA	dc
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as
shown in the figure.
•	 WARNING:	
	 A	SEAL	SHALL	BE	INSTALLED	WITHIN	50cm	OF	
THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
•	 WARNING:			
	 WHEN	INSTALLED	IN	CL.I,	DIV	2,	SEAL	NOT	
REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2, AUCUN
JOINT N'EST REQUIS.
Non-hazardous
Location Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
SUPPL
Y
PULSE
CHECK
ALARM
Transmitter
F0208.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
SUPPL
Y
PU
LS
E
CHECK
ALARM
Transmitter
F0209.ai
H
an
dlin
g C
au
tio
ns
2