3 wiring, Wiring, 1 loop configuration – Yokogawa EJX115A User Manual
Page 32: 2) intrinsically safe type, Simultaneous analog-pulse output, Figure 5.5 external temperature connection
 
<5. Wiring>
30
IM 01C25A01-01E
5.2.5 External Temperature Connection
(for EJX910A and EJX930A)
Connect the RTD cable assembly to the Juck Terminal.
F0505.ai
SUPPL
Y
PULSE
CHECK
ALARM
Figure 5.5
External Temperature Connection
5.3 Wiring
5.3.1 Loop Configuration
Since	the	DPharp	uses	a	two-wire	transmission	system,	
signal	wiring	is	also	used	as	power	wiring.
DC	power	is	required	for	the	transmitter	loop.	The	
transmitter	and	distributor	are	connected	as	shown	below.
For	details	of	the	power	supply	voltage	and	load	
resistance,	see	Section	5.6.
(1) General-use Type and Flameproof Type
• Analog Output
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
F0506.ai
SUPPL
Y
PULSE
CHECK
ALARM
Figure 5.6
Connection between Transmitter and
Distributor
• Pulse output and Alarm, Status Output or
Simultaneous Analog-Pulse Output
(for EJX910A and EJX930A)
SUPPL
Y
PULSE
CHECK
ALARM
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
Receiver
instrument
F0507.ai
Figure 5.7
Connection between Transmitter and
Distributor
(2) Intrinsically Safe Type
With	the	intrinsically	safe	type,	a	safety	barrier	must	be	
included	in	the	loop.
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
Safety barrier
F0508.ai
SUPPL
Y
PULSE
CHECK
ALARM
Figure 5.8
Connection between Transmitter and
Distributor
(3) Intrinsically Safe Type (for EJX910A and
EJX930A)
• Analog Output
SUPPL
Y
PULSE
CHECK
ALARM
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Receiver instrument
(and power supply)
Safety barreir
(Isolation type)
F0509.ai
Anaolg input
Power
supply
• Simultaneous Analog-Pulse Output
SUPPL
Y
PULSE
CHECK
ALARM
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Safety barrier
(Isolated type)
I/O module
F0510.ai
Safety barrier
(Isolated type)
Power
supply
Power
supply
Analog input
Pulse input
Figure 5.9
Connection between Transmitter,