Caution, 3 cable connection rtd terminal box side – Yokogawa EJX115A User Manual
Page 35
 
<5. Wiring>
33
IM 01C25A01-01E
5.4.2 Connecting Shielded Cable for
Conduit Use (External temperature
input code: -B, -C, and -D)
• RTD connection components: EJX multivariable
transmitter and RTD cable
F0522.ai
Procedure
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.
SUPPL
Y
PULSE
CHECK
ALARM
F0523.ai
(2) Remove the cap protecting the connecting port. Then
insert	the	RTD	cable	and	firmly	plug	the	connector	
into	the	connecting	port	in	the	transmitter's	terminal	
box.
(3) Insert the cable through the conduit and attach it to
the RTD electrical connection.
CAUTION
Do	not	pull	the	cable	or	subject	it	to	excessive	
mechanical	shock.
5.4.3 Cable Connection RTD Terminal Box
Side
EJX	multivariable	transmitter	RTD	I/F	is	for	3-wire	Type	
RTD,	Pt100.	
Heed	the	following	when	wiring	an	RTD	of	the	2-	or	4-wire	
type.		
NOTE
Please	note	that	a	temperature	error	will	occur	when	
you	use	a	2-wire	RTD	because	of	wiring	resistance.	
Please	do	not	ground	the	shield	on	the	RTD	side	of	
the	cable.	
CAUTION
Please	use	only	the	cables	provided	with	this	
instrument.	
When	wiring,	be	sure	not	to	damage	the	cable's	
insulation	or	its	core.	
All	the	cable	cores	must	have	sufficient	insulation	
around	them.	
Do	not	let	the	signal	line	contact	the	shield	line.		
Do	not	allow	the	shield	line	or	the	signal	line	to	come	
the	earth	potential	voltage.
2-Wire
3-Wire
4-Wire
A
B A
B b A
B b
a
F0524.ai
Figure 5.13 The Method of Wiring for the RTD Side
Table 5.2
The Method of Wiring for the RTD Side
RTD Terminal
RTD Terminal
A
a
B
b
2-Wire
White
-
Blue1 and Blue2
-
3-Wire
White
-
Blue1
Blue2
4-Wire
White open
Blue1
Blue2
NOTE
The	color	display	in	the	table	shows	the	white	line	of	
the	cable.		
The	cable	color	could	change	depending	on	the	cable	
type.	
Blue	1	and	blue	2	allow	changing	places.	
For	2-wire	Type,	connect	either	which	is	blue1	or	
blue2,	and	give	other	side	as	OPEN.
W
irin
g
5