3 diaphragm seals installation consideration, Diaphragm seals installation consideration, Important – Yokogawa EJX115A User Manual
Page 21
 
<3. Installation>
19
IM 01C25A01-01E
3.2.1 EJ210
The	transmitter	is	mounted	on	a	process	using	its	
high	pressure	side	flange	as	shown	in	Figure	3.5.	The	
customer	should	prepare	the	mating	flange,	gasket,	stud	
bolts	and	nuts.
F0305.ai
Gasket
Stud bolt
Nut
Figure 3.5
EJ210 Mounting
3.2.2 EJ118 and EJ438
Mount	the	diaphragm	seals	using	the	flanges	as	shown	in	
Figure	3.6.	The	mating	flange,	gasket,	bolts	and	nuts	are	
to	be	procured	by	the	customer.
Nut
Flange
Diaphragm
ød
Gasket
F0306.ai
Bolt
The product is
shipped with these
parts assembled.
Correctly install the diaphragm
seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW).
Figure 3.6
Mounting the Diaphragm Seals
3.3 Diaphragm Seals Installation
Consideration
IMPORTANT
• When measuring the liquid level of the tank, the
minimum	liquid	level	(zero	point)	must	be	set	to	a	
level	at	least	50	mm	above	the	center	of	the	high	
pressure	side	diaphragm	seal	(see	Figure	3.7).
• Correctly install the diaphragm seals on the high
and	low	pressure	sides	of	the	process,	checking	
the	label	on	each	seal.
• To avoid measuring error duets temperature
difference	between	the	two	diaphragm	seals,	
capillary	tube	must	be	bound	together.	The	
capillary	tube	must	be	securely	fixed	to	the	tank	
wall	to	prevent	movement	by	wind	or	vibration.		
If	the	capillary	tube	is	too	long,	loosely	coil	the	
extra	tube	portion	(coil	diameter	of	300	mm	or	
more)	and	secure	the	coiled	tube	with	a	clamp.
F0307.ai
50 mm minimum
Minimum
liquid level
High
pressure
side
Low
pressure
side
The transmitter should
be installed as low as
possible below the
position where the high
pressure side
diaphragm seal is
installed.
Install the sealed diaphragm
so that the shank positions
downward.
IMPORTANT
Figure 3.7
Installing the Diaphragm Seals to a
Tank
In
sta
lla
tio
n
3